5587001-YSG-A-520 | Start-Up & Operation Guide
Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
Circ1ClgOATCutout
AV
Circ2ClgOATCutout
AV
Freeze-Sp
AV
ClgDATUp-SP
AV
ClgDATLo-SP
AV
OprClgDAT-SP
AV
ClgOcc-Sp
AV
ClgUnocc-Sp
AV
OprClg-Sp
AV
C1A-RunTime
AV
C1B-RunTime
AV
C2A-RunTime
AV
C1AOnTimer
AV
C1BOnTimer
AV
C2AOnTimer
AV
C1A-ASCDTmr
AV
C1B-ASCDTmr
AV
C2A-ASCDTmr
AV
100
Object
Read/
Short Description
ID
Write
29581
R/W
Circ1ClgOATCutout
29582
R/W
Circ2ClgOATCutout
29592
R/W
Freeze-Sp
29604
R/W
ClgDATUp-SP
29605
R/W
ClgDATLo-SP
29607
R
OprClgDAT-SP
29608
R/W
ClgOcc-Sp
29609
R/W
ClgUnocc-Sp
29610
R
OprClg-Sp
29627
R
C1A-RunTime
29628
R
C1B-RunTime
29630
R
C2A-RunTime
29631
R
C1AOnTimer
29632
R
C1BOnTimer
29634
R
C2AOnTimer
29635
R
C1A-ASCDTmr
29636
R
C1B-ASCDTmr
29638
R
C2A-ASCDTmr
Long
Point Definitions (Units)
Description
Circuit 1 compressors are disabled
Circuit 1 OAT
when OAT drops below this setpoint
Cooling Cutout
(...75.0°F)
Circuit 2 compressors are disabled
Circuit 2 OAT
when OAT drops below this setpoint
Cooling Cutout
(...75.0°F)
A BAS command to disable cooling
Freeze Condition
to prevent cooling coil from freezing
Setpoint
(20.0–32.0°F)
Cooling DAT
The upper setpoint for the DAT reset
Upper Setpoint
schedule (41.0–80.0°F)
Cooling DAT
The lower setpoint for the DAT reset
Lower Setpoint
schedule (40.0–79.0°F)
Operating Cooling
Displays the active DAT setpoint (°F)
DAT Setpoint
OCC Cooling
The occupied cooling setpoint
Setpoint
(45.0–98.0°F)
UNOCC Cooling
The unoccupied cooling setpoint
Setpoint
(46.0–99.0°F)
Operating Cooling
Displays the active operating cooling
Setpoint
setpoint (0.0–100.0°F)
Compressor
Displays the operating hours of
Accumulated
compressor 1A (hours)
Runtime 1A
Compressor
Displays the operating hours of
Accumulated
compressor 1B (hours)
Runtime 1B
Compressor
Displays the operating hours of
Accumulated
compressor 2A (hours)
Runtime 2A
Displays the minimum time
Min. ON Time
remaining for compressor 1A to turn
Remaining 1A
off (seconds)
Displays the minimum time
Min. ON Time
remaining for compressor 1B to turn
Remaining 1B
off (seconds)
Displays the minimum time
Min. ON Time
remaining for compressor 2A to turn
Remaining 2A
off (seconds)
Anti-Short Cycle
Displays the time remaining for
Delay Time
compressor 1A to turn on (seconds)
Remaining 1A
Anti-Short Cycle
Displays the time remaining for
Delay Time
compressor 1B to turn on (seconds)
Remaining 1B
Anti-Short Cycle
Displays the time remaining for
Delay Time
compressor 2A to turn on (seconds)
Remaining 2A