York Sun Premier GZA1M Series Start-Up & Operation page 107

Rooftop units
Table of Contents

Advertisement

Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
SatSucTemp2
AV
H8-Starts
AV
DehumEvapLowSp
AV
Name
CSV
Serial#
CSV
FirmVer
CSV
DevName
CSV
Htg-Type
MV
ExFType
MV
Y1-Tstat
MV
Y2-Tstat
MV
W1-Tstat
MV
W2-Tstat
MV
G-Tstat
MV
Occ-Tstat
MV
Tstat-Only
MV
OccSrc
MV
YORK
Object
Read/
Short Description
ID
Write
30055
R
SatSucTemp2
30056
R
H8-Starts
30061
R/W
DehumEvapLowSp
29804
R/W
Name
29806
R/W
Serial#
29807
R
FirmVer
29818
R/W
DevName
29501
R/W
Htg-Type
29503
R/W
ExFType
29504
R
Y1 - Thermostat
29505
R
Y2 - Thermostat
29508
R
W1 - Thermostat
29509
R
W2 - Thermostat
29511
R
G - Thermostat
29512
R
OCC
29514
R/W
Tstat-Only
29515
R
OccSrc
Start-Up & Operation Guide | 5587001-YSG-A-520
Long
Point Definitions (Units)
Description
Saturated Suction
Displays the active system 2 saturated
Temperature 2
suction line temperature (°F)
Heating Number
Displays the heating start counts for
Times ON 8
stage 8
A BAS command to adjust
Dehum Evap Low
dehumidification evaporator low
Setpoint
setpoint (40°F)
Unit Name
Displays the unit name
Unit Serial
Displays the unit serial number
Number
Firmware Version
Displays the firmware version
Device Name
A BAS command to input device name
A BAS command to select the current
operating mode:
0 = none
Heating Control
1 = gas
Type
2 = electric
3 = hot water
4 = steam
A BAS command to select the current
operating mode:
0 = none
Exhaust Type
1 = barometric
2 = modulating damper
3 = VFD
Displays the thermostat call for stage
Y1 - Thermostat
1 cooling
Displays the thermostat call for stage
Y2 - Thermostat
2 cooling
Displays the thermostat call for stage
W1 - Thermostat
1 heating
Displays the thermostat call for stage
W2 - Thermostat
2 heating
Displays the thermostat call of supply
G - Thermostat
fan
0 = OFF 1 = ON
Displays the status of the occupancy
input
Occupancy Input
0 = disabled/UNOCC
1 = enabled/OCC)
A BAS command that allows control
Thermostat Only
of unit by thermostat
Control Enabled
0= NO 1 = YES
Displays the OCC/UNOCC status
with the selected input source
0 = local input
Occupancy Input
1 = local network sensor
Source
2 = BAS network request
3 = local schedule
4 = temporary occupancy
0 = OFF 1 = ON
0 = OFF 1 = ON
0 = OFF 1 = ON
0 = OFF 1 = ON
107