Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
OprSSO
AV
NetSSO
AV
OprOAT
AV
NetOAT
AV
OprOAH
AV
OA-Enth
AV
NetOAH
AV
OprOAQ
AV
NetOAQ
AV
FanVFD
AV
Fan-RT
AV
FanOffDlyCool
AV
FanOffDlyHeat
AV
DAT
AV
DctPrs
AV
DctPrs-Sp
AV
DctShutdownSp
AV
#ClgStgs
AV
MinRtCoolStg
AV
YORK
Object
Read/
Short Description
ID
Write
29537
R
OprSSO
29540
R/W
NetSSO
29541
R
OprOAT
29543
R/W
NetOAT
29544
R
OprOAH
29545
R
OA-Enth
29546
R/W
NetOAH
29547
R
OprOAQ
29549
R/W
NetOAQ
29551
R
SF-O
29554
R
SF-Runtime
29559
R/W
FanOffDlyCool
29561
R/W
FanOffDlyHeat
29564
R
DAT
29565
R
DA-P
29566
R/W
DctPrs-Sp
29567
R/W
DctShutdownSp
29576
R
#ClgStgs
29578
R
MinRtCoolStg
Start-Up & Operation Guide | 5587001-YSG-A-520
Long
Point Definitions (Units)
Description
Operational Zone
Displays the operational zone
Temperature
temperature setpoint offset (Δ°F)
Setpoint Offset
Network Override
A BAS command to override space
Space Setpoint
setpoint offset (-5.0 to 5.0 Δ°F)
Offset
Operational OAT
Displays the active OAT (°F)
Network Override
A BAS command to override OAT
OAT
(-50.0 to 125.0°F)
Operational
Displays the active outside air
Outdoor Air
humidity (%RH)
Humidity
Outdoor Air
Displays the active outside air
Enthalpy
enthalpy (BTU/lb)
Network Override
A BAS command to override outside
Outdoor Air
air humidity (0–100 %RH)
Humidity
Operational
Displays the active outdoor air CO
Outdoor Air
(PPM)
Quality
Network Override
A BAS command to override outdoor
Outdoor Air
air CO
(PPM)
Quality
2
Displays the output from the control
Fan % Command
to the supply fan VFD (%)
Supply Fan
Displays the supply fan runtime
Accumulated
(hours)
Runtime
A BAS command to adjust the supply
Fan Off Delay for
fan runtime after cooling is turned
Cool
OFF (0–255 seconds)
A BAS command to adjust the supply
Fan Off Delay for
fan runtime after heating is turned
Heat
OFF (0–30 seconds)
DAT
Displays the active DAT (°F)
Discharge Air
Displays the active discharge air
Static Pressure
static pressure (iwg)
Duct Pressure
A BAS command to adjust active
Setpoint
duct static pressure setpoint (iwg)
Duct Pressure
A BAS command to adjust the
Shutdown
duct static pressure unit shutdown
Setpoint
setpoint (iwg.)
Number of
Displays the number of cooling
Cooling Stages
stages installed.
Installed
Minimum Runtime
Displays the minimum runtime for a
for a Cooling
cooling stage (3–10 minutes)
Stage
2
99