Table 24: Modulating Gas Heating Faults List - York Sun Premier GZA1M Series Start-Up & Operation

Rooftop units
Table of Contents

Advertisement

• When flame rectification is established, the con-
troller enters a warm-up cycle to ensure flame sta-
bilization and to reduce condensation forming in
the heat exchanger
• After completing the warm-up cycle, the controller
enters the run cycle
• During the run cycle, the burner firing rate
and draft inducer pressure are determined
based on the heating demand sent via Mo-
dus from the unit controller
• The unit controller determines when more
or less heating capacity is needed and com-
municates this via Modbus to the modulating
gas controller
• The run cycle terminates when
• The heating demand is removed

Table 24: Modulating Gas Heating Faults List

LED Display
Diagnostic Code
888
1
OFF
2
Pur
16n
3
HEA
run
rEt
4/5
A01
4
A02
5
A03
6
A04
7
A05
8
A06
9
A07
33
A08
34
A11
24
A15
10
E01
11
E02
12
E03
13
E04
14
E05
15
E08
18
E09
19
E13
23
E18
22
Ed
20
None
None
YORK
Type
Lockout
Board failure (also during power up)
Status
UP mode: burner state = OFF
Status
UP mode: burner state = Purge
Status
UP mode: burner state = Ignition
Status
UP mode: burner state = Warm-up
Status
UP mode: burner state = Run
Status
UP mode: burner state = Retry
Alert
Failed ignition attempt
Alert
Lost flame
Alert
Insufficient combustion air—auto-derating
Alert
Limited low fire (due to lost flame auto adaption)
Alert
Weak flame signal, main burner
Alert
Reserved
Alert
Air modulating failure (inducer isn't modulating down)
Alert
Air sensor null pressure check (out of tolerance)
Alert
Failed ignition, split manifold burner, retries exhausted
Alert
Weak flame signal, one or more split manifold staged burners
Lockout
Failed ignition, retries exhausted
Lockout
Primary limit failure (or open fuse)
Lockout
Modulating valve failure
Air pressure sensor reading low (pressure switch failed to open or
Lockout
insufficient air/blocked vent)
Lockout
Air pressure sensor reading high (pressure switch failed to close)
Lockout
Unexpected flame, main burner
Lockout
No R-W enable signal during CFH
Lockout
Open fuse
Lockout
Unexpected flame, split manifold burner
Lockout
Invalid ID, plug installed
Lockout
Board not receiving 24 volts
Start-Up & Operation Guide | 5587001-YSG-A-520
• Any of the gas heat safeties open
• The control reaches its maximum runtime
of 6 hours. When this limit is reached, the
control terminates the run cycle and im-
mediately re-enters heating operation
when a heating demand still exists
• After terminating the run cycle, the 2-stage gas
valve closes and the modulating gas valve returns
to a set position
• The inducer is controlled to the light-off setting for
a 45-second post-purge cycle
• After completing the post-purge cycle, the control-
ler enters the off cycle. In the off cycle, all outputs
are de-energized but all safeties are still monitored
• When more heating capacity is needed, the unit
controller starts staging on other burners (2, 3, or
1B)
Description
55