York Sun Premier GZA1M Series Start-Up & Operation page 102

Rooftop units
Table of Contents

Advertisement

5587001-YSG-A-520 | Start-Up & Operation Guide
Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
MATClgLim
AV
Econ-MinPos
AV
MAT
AV
DAH
AV
RA-Enth
AV
RAT
AV
DVentMaxEconPos
AV
DVentIAQ-Sp
AV
DVentDiff-Sp
AV
ExFanVFD
AV
ExF-RunTim
AV
Bldg-Sp
AV
BldgPres
AV
EAD-O
AV
ExDmpPosFanOn
AV
ExDmpPosFanOff
AV
HGR
AV
Dehum-SP
AV
102
Object
Read/
Short Description
ID
Write
29755
R/W
MATClgLim
29759
R/W
Econ-MinPos
29760
R
MAT
29762
R
DAH
29763
R
RA-Enth
29764
R
RAT
29766
R/W
DVentMaxEconPos
29767
R/W
DVentIAQ-Sp
29768
R/W
DVentDiff-Sp
29776
R
EF-O
29779
R
ExF-RunTim
29780
R/W
Bldg-Sp
29781
R
BldgPres
29782
R
EAD-O
29783
R/W
ExDmpPosFanOn
29784
R/W
ExDmpPosFanOff
29790
R
HGR
29792
R/W
Dehum-SP
Long
Point Definitions (Units)
Description
Mixed Air
A BAS command to limit outside air
Temperature
damper to prevent MAT below this
Cooling Limit
value (0.0–100.0°F)
Economizer
A BAS command to adjust minimum
Minimum Position
outside air damper position (0–100 %)
Setpoint
Mixed Air
Displays the active MAT (°F)
Temperature
Discharge Air
Displays the active discharge air
Humidity
humidity (%RH)
Return Air
Displays the active return air
Enthalpy
enthalpy (BTU/lb)
Return Air
Displays the active RAT (°F)
Temperature
Demand
Ventilation
A BAS command to adjust maximum
Maximum
demand ventilation economizer
Economizer
position (%)
Position
Demand
A BAS command to adjust IAQ (CO
Ventilation IAQ
demand ventilation setpoint (0–5,000
Setpoint
PPM)
Demand
A BAS command to adjust demand
Ventilation
ventilation (CO
Differential
(0–5,000 PPM)
Setpoint
Exhaust Fan VFD
Displays the status of exhaust/return
% Command
fan VFD command (%)
Exhaust Fan
Displays the exhaust/return fan
Accumulated
runtime (hours)
Runtime
Building Pressure
A BAS command to adjust building
Setpoint
pressure setpoint (-0.25 to 0.25 iwg)
Building Static
Displays active building static
Pressure
pressure (iwg)
Exhaust Damper
Displays the status of exhaust
% Command
damper command (%)
Exhaust Damper
A BAS command to enable exhaust
Position for
fan based on exhaust damper
Exhaust Fan to
position (20–99%)
Turn ON
Exhaust Damper
A BAS command to disable exhaust
Position for
fan based on exhaust damper
Exhaust Fan to
position (20–99%)
Turn OFF
The commanded HGRH valve
HGRH Command
position (%)
Dehumidification
A BAS command to adjust
Setpoint
dehumidification setpoint (0–100 %RH)
)
2
) differential setpoint
2
YORK

Advertisement

Table of Contents
loading

Table of Contents