Table 28: BACnet IP Settings (Continued)
Description
Read-only status of the IP mask in
IP Mask
use
IP Router
Read-only status of the IP router
Address
address in-use

Table 29: BACnet MS/TP Settings

Description
The MS/TP MAC address of the unit
you select must not conflict with any
other MS/TP device on the same wire.
Address
For other field devices connected to
the same RS-485 bus, use sequential
addressing. No single MAC address
can be used by more than one device
The RS-485 BACnet connection
requires a specified baud rate in order
Baud
to initiate communication with field
Rate
devices that may use auto-baud rate
configuration
The device ID is the instance number
Device
for the BACnet device. This number
OID
must be unique across the building
networks for all device instances

Mobile Access Portal (MAP) Gateway

The mobile access portal (MAP) gateway provides a
wireless mobile user interface to the Smart Equipment.
The MAP gateway gives access to any Smart Equip-
ment device that is on a connected BACnet (MS/TP)
field bus. The intuitive, browser-based interface dis-
plays the same menus as the local user interface.
NOTE: The Applied Smart Equipment controller is only
compatible with MAP 5.0 and above.
For related documentation, including how to set up param-
eters, and training videos, visit uLearn at
kzoplatform.com/containers/957891534378768109?.

Table 30: MAP Gateway Related Documentation

Topic
Getting up and running
Mobile Access Portal Gateway
quickly with the MAP
Quick Start Guide
gateway
(Part No. 24-10737-16)
Mobile Access Portal Gateway
Installing and wiring a
Installation Instructions
MAP gateway
(Part No. 24-10737-8)
YORK
BACnet IP – Dynamic
IP Address
Read-only status of the
IP mask in use
Read-only status of the
IP router address in use
Wired Field
Bus
Set to
the MAC
address
reserved for
the unit
Set to the
baud rate of
the trunk
Set to the
device OID
reserved for
the unit
https//jcpublic.
Document

Figure 43: MAP Gateway Dashboard

Start-Up & Operation Guide | 5587001-YSG-A-520
User Action or Recommended Setting
BACnet IP – Static IP
Address
Read-only status of the
IP mask in use
Read-only status of the
IP router address in use
User Action or Recommended Setting
Wireless
N2 Field
Field Bus
Bus
Set to
Set to
the MAC
the MAC
address
address
reserved for
reserved for
the unit
the unit
(not used)
(not used)
Set to the
device OID
(not used)
reserved for
the unit
Default/Range
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
Modbus
Default/
Field Bus
Range
Set to
the MAC
address
4 / 4–255
reserved for
the unit
(not used)
38400 bps
(not used)
0–4194302
LD28042
97