York Sun Premier GZA1M Series Start-Up & Operation page 81

Rooftop units
Table of Contents

Advertisement

Table 26: Menus and Submenus (Continued)
Menu
Submenu
Htg > Setup
Details
(Figure 31)
Htg > Service
> Unit
Htg > Service
> Stage 1–
Stage 8
YORK
Parameters Displayed / Default
ZT-ResetSpUpper (ZT Reset Setpoint
Upper)
SF-DAT-SpHighThresh (Supply Fan
DAT Setpoint High Threshold)
SF-DAT-SpLowThresh (Supply Fan DAT
Setpoint Low Threshold)
HtgAdapTunEn (Heating Adaptive
Tuning Enable)
HtgOATCutout-Sp (Outside Air
Temperature Heating Cutout Setpoint)
MornW-En (Morning Warm-Up Enabled)
MornWRAT-Sp (Morning Warm-Up/
Return Air Temperature Setpoint)
MornWDAT-Sp (Morning Warm-Up
Discharge Air Temperature Setpoint)
HtgUnocc-En (Unoccupied Heating
Enabled)
HtgOcc-En (MZVAV Occupied Heating
Enabled)
DATTemper-En (Discharge Air
Temperature Tempering Enable)
DATTemper-Sp (Discharge Air
Temperature Tempering Setpoint)
StgHtgCmd (Staged Heating Command)
Htg-S (Heating Status)
OprHtg-Sp (Operating Heating Setpoint)
OprHtgDAT-SP (Operating Heating
Discharge Air Temperature Setpoint)
OprOAT (Operational Outside Air
Temperature)
OprZT (Operational Zone Temperature)
RAT (Return Air Temperature)
W1 - Thermostat
W2 - Thermostat
DAT (Discharge Air Temperature)
HE-T (Heat Entering Temperature)
HET-Alarm (Heat Entering Temperature
Sensor Alarm)
DATTempState (DAT Tempering State)
H1-S (Heating Stage 1 Status)
Start-Up & Operation Guide | 5587001-YSG-A-520
Conditions for Parameters Displayed
Units / Range
deg F (61–131)
% (0–100)
% (0–100)
No, Yes
deg F (0–100)
No, Yes
deg F (50–85)
deg F (85–135)
No, Yes
No, Yes
No, Yes
deg F (40–60)
%
OFF-Idle, ON, SAT Tempering, Morning Warm-
Up, Thermostat Heating, Unoccupied Heating,
Occupied Heating, OFF-Disabled, OFF-OAT
Lockout, OFF-SAT Limit, OFF-Waiting for
Changeover Delay, Comfort Ventilation
deg F
deg F
deg F
deg F
deg F
OFF, ON
OFF, ON
deg F
deg F
Normal, Alarm
Disable, Enable
OFF-Idle, ON-Minimum Runtime Timer, ON-Normal
Command, OFF-Heating is Disabled, OFF-Gas
Valve Lost Proof, OFF-Gas Valve False Proof,
OFF-Heating Limit Lockout, OFF-Anti-Short Cycle
Timer, OFF-Heating Stage is Disabled