NOTE: The unit restarts after the restoration file is re-
stored. It is not recommended to perform a re-
store during critical operation times.

Figure 38: Update-Restore Menu

Failed Restore Attempt
When the flash drive is removed before the firmware
upload is allowed to complete, it requires that the user
perform two updates/upload procedures to successful-
ly complete and update all the necessary files. When
power is lost during the upload process, the user is
only required to repeat one update/upload procedure.

Full Clone Function

The full clone function is intended for "copy-and-paste"
setup of multiple, similar units. This process copies all
values from the flash drive restoration file to the main
control board except those listed below.
• Device name
• Unit name
• Unit model number
• Unit serial number
• Fan accumulated runtime
• Address
• Time zone
• Device old
• Compressor stage X accumulated runtime
• Heating stage X accumulated runtime
Restoration files must be placed in the top level of the
flash drive storage. The unit serial number value in the
restoration file does not need to match the unit serial
number value of the main control board to be cloned.
The functionality and setup of this function is similar to
the Simplicity Smart Equipment (SSE) controller.

Partial Clone Function

The partial clone function is intended for "copy-and-
paste" setup of multiple, similar units. This process cop-
ies only a limited set of parameters listed below from the
flash drive restoration file to the main control board.
YORK
Start-Up & Operation Guide | 5587001-YSG-A-520
• Duct pressure setpoint
• Duct pressure shutdown setpoint
• Continuous supply fan operation in OCC mode
• Turn OFF continuous fan operation when starting
heat
• Occupied: No heat or cool % command
LD28370
• Occupied: X stage of cool % command
• Occupied: X stage of heat % command
• MZVAV cooling SAT user setpoint
• MZVAV cooling SAT lower setpoint
• MZVAV SAT reset setpoint
• MZVAV operating cooling SAT setpoint
• SZVAV occupied cooling setpoint
• SZVAV unoccupied cooling setpoint
• MZVAV occupied heating enabled
• MZVAV occupied heating setpoint
• MZVAV unoccupied heating enabled
• MZVAV unoccupied heating setpoint
• Morning warm-up enabled
• Morning warm-up/return air temperature setpoint
• SZVAV occupied heating setpoint
• SZVAV unoccupied heating setpoint
• Low ambient economizer setpoint
• Low ambient economizer minimum position
• Language
• Units
• BAS communication
Restoration files must be placed in the top level of the
flash drive storage. The unit serial number value in the
restoration file does not need to match the unit serial
number value of the main control board to be cloned.
The functionality and setup of this function is similar to
the Simplicity Smart Equipment (SSE) controller.