York 13 Seer-TCG Installation Manual

York 13 Seer-TCG Installation Manual

Outdoor split-system air conditioning

Advertisement

INSTALLATION MANUAL

R-410A
OUTDOOR SPLIT-SYSTEM

AIR CONDITIONING

MODELS: 13 & 14.5 SEER -
TCG(D,F)/GCGD/TCJ(D,F)/YCJ(D,F) SERIES
1.5 TO 5 TONS - 1 & 3 PHASE
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . '1
SAFETY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
UNIT INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
ORIFICE INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
TXV INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Typical Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Installation of Vapor Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Underground Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Heat Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Orifice Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Outdoor Unit Control Box (Single Phase) . . . . . . . . . . . . . . . . . . . . . .7
Outdoor Unit Control Box (Three Phase) . . . . . . . . . . . . . . . . . . . . . . .7
Application Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
SECTION I: GENERAL
The outdoor units are designed to be connected to a matching indoor
coil with sweat connect lines. Sweat connect units are factory charged
with refrigerant for a matching indoor coil plus 15 feet of field-supplied
lines.
The refrigerant charge may need to be changed for some indoor-out-
door unit combinations, elevation differences or total line lengths. Refer
to Application Data covering "General Piping Recommendations and
Refrigerant Line Length" (Part Number 247077).
SECTION II: SAFETY
This is a safety alert symbol. When you see this symbol on
labels or in manuals, be alert to the potential for personal
injury.
Understand and pay particular attention to the signal words DANGER,
WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not
avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not
avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not
avoided may result in minor or moderate injury. It is also used to
alert against unsafe practices and hazards involving only property dam-
age.
This product must be installed in strict compliance with the
enclosed installation instructions and any applicable local, state,
and national codes including, but not limited to building, electrical,
and mechanical codes.
Johnson Controls Unitary Products
LIST OF SECTIONS
EVACUATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
SYSTEM CHARGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
INSTRUCTING THE OWNER . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
LIST OF FIGURES
Wiring Diagram - Single Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Wiring Diagram - Three Phase . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
LIST OF TABLES
R-410A Saturation Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
R-410A systems operate at higher pressures than R-22 systems.
Do not use R-22 service equipment or components on R-410A
equipment. Service equipment
Improper installation may create a condition where the operation of
the product could cause personal injury or property damage.
Improper installation, adjustment, alteration, service or mainte-
nance can cause injury or property damage. Refer to this manual
for assistance or for additional information, consult a qualified con-
tractor, installer or service agency.
INSPECTION
As soon as a unit is received, it should be inspected for possible dam-
age during transit. If damage is evident, the extent of the damage
should be noted on the carrier's delivery receipt. A separate request for
inspection by the carrier's agent should be made in writing. See Local
Distributor for more information.
Requirements For Installing/Servicing R-410A Equipment
• Gauge sets, hoses, refrigerant containers, and recovery system
must be designed to handle the POE type oils, and the higher
pressures of R-410A.
• Manifold sets should be high side and low side with low side
retard.
• All hoses must have a 700 psig service pressure rating.
• Leak detectors should be designed to detect HFC refrigerant.
• Recovery equipment (including refrigerant recovery containers)
must be specifically designed to handle R-410A.
• Do not use an R-22 TXV.
• A liquid-line filter drier is required on every unit.
®
Must Be Rated
for R-410A.
835964-UIM-A-0112

Advertisement

Table of Contents
loading

Summary of Contents for York 13 Seer-TCG

  • Page 1: Table Of Contents

    INSTALLATION MANUAL R-410A OUTDOOR SPLIT-SYSTEM AIR CONDITIONING MODELS: 13 & 14.5 SEER - ® TCG(D,F)/GCGD/TCJ(D,F)/YCJ(D,F) SERIES 1.5 TO 5 TONS – 1 & 3 PHASE LIST OF SECTIONS GENERAL ..........‘1 EVACUATION .
  • Page 2: Unit Installation

    835964-UIM-A-0112 LIMITATIONS If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or The unit should be installed in accordance with all National, State and ground to avoid taking the accumulated layer of hot air into the outdoor Local Safety Codes and the limitations listed below: unit.
  • Page 3: Installation Of Vapor Line

    835964-UIM-A-0112 GROUND INSTALLATION The unit should be installed on a solid base that is 2” (5.1 cm) above grade and will not shift or settle, causing strain on the refrigerant lines This system uses R-410A refrigerant which operates at higher pres- and possible leaks.
  • Page 4: Heat Protection

    835964-UIM-A-0112 PRECAUTIONS DURING BRAZING OF LINES All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such Do not install any coil in a furnace which is to be operated during as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units the heating season without attaching the refrigerant lines to the coil.
  • Page 5: Orifice Installation

    835964-UIM-A-0112 SECTION IV: ORIFICE INSTALLATION Only 1TVM900 series valves are to be used on this product. Relieve the holding charge by pulling off the rubber cap plug on Failure to install Schrader Valve Core on orifice applications could result in total refrigerant loss of the system! the suction manifold line of the coil.
  • Page 6: System Charge

    835964-UIM-A-0112 SECTION VII: SYSTEM CHARGE Using the charging chart located on the unit, find the intersection of the outdoor ambient dry bulb and the suction pressure obtained The factory charge in the outdoor unit includes enough charge for the in step 3. This is the recommended suction tube temperature at unit, a 15 ft.
  • Page 7: Outdoor Unit Control Box (Single Phase)

    835964-UIM-A-0112 TABLE 2: R-410A Saturation Properties PRESSURE PRESSURE PRESSURE PRESSURE PRESSURE TEMP. °F TEMP. °F TEMP. °F TEMP. °F TEMP. °F PSIG PSIG PSIG PSIG PSIG 326. SECTION VIII: ELECTRICAL Contactor CONNECTIONS GENERAL INFORMATION & GROUNDING Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label.
  • Page 8: Typical Field Wiring (Air Handler / Electrical Heat) (Single-Phase)

    835964-UIM-A-0112 FIELD CONNECTIONS CONTROL WIRING Mount the thermostat about 5 ft. above the floor, where it will be exposed to normal room air circulation. Do not place it on an out- Route low voltage wiring into bottom of control box as shown in side wall or where it is exposed to the radiant effect from exposed Figure 6.
  • Page 9: Thermostat Chart - Single Stage Ac With Psc Air Handler

    835964-UIM-A-0112 For additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document available online at www.upgnet.com in the Product Catalog Section. AC 1A Single Stage Air Conditioner – PSC Air Handler ID MODELS THERMOSTAT SINGLE STAGE SINGLE STAGE *PP11C70224 AIR HANDLER...
  • Page 10: Thermostat Chart - Single Stage Ac With Psc Air Handler

    835964-UIM-A-0112 AC 1B Single Stage Air Conditioner – PSC Air Handler ID MODELS THERMOSTAT THERMOSTAT *BP11C50124 SINGLE STAGE *BN11C01124 *BN11C00124 *DP11C40124 AIR HANDLER CONDITIONER *DN11C00124 SINGLE STAGE AIR HANDLER CONTROL AIR CONDITIONER 24 – Volt Common 24 – Volt Common 24 –...
  • Page 11: Thermostat Chart - Single Stage Ac With Psc Furnace

    835964-UIM-A-0112 AC 5D Single Stage Air Conditioner – Single Stage PSC Furnace ID MODELS G*(8/9)S GF(8/9) G*9F L(Y/M)8S TG(8/9)S THERMOSTAT (G/T)GLS SINGLE STAGE SINGLE STAGE *PP11C70224 FURNACE CONDITIONER SINGLE STAGE PSC SINGLE STAGE SINGLE STAGE FURNACE AIR CONDITIONER AIR CONDITIONER 24 –...
  • Page 12: Thermostat Chart - Single Stage Ac With Psc Furnace

    835964-UIM-A-0112 AC 5E Single Stage Air Conditioner – Single Stage PSC Furnace ID MODELS G*(8/9)S GF(8/9) G*9F L(Y/M)8S TG(8/9)S THERMOSTAT THERMOSTAT (G/T)GLS *BP11C50124 SINGLE STAGE SINGLE STAGE *BN11C01124 *BN11C00124 *DP11C40124 FURNACE CONDITIONER *DN11C00124 SINGLE STAGE PSC SINGLE STAGE FURNACE AIR CONDITIONER 24 –...
  • Page 13: Instructing The Owner

    835964-UIM-A-0112 SECTION IX: INSTRUCTING THE OWNER 3. If the coil needs to be cleaned, use clean water to wash dust, dirt, and debris from outdoor condensing coil. Assist owner with processing warranty cards and/or online registration. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance.
  • Page 14: Wiring Diagram

    835964-UIM-A-0112 SECTION X: WIRING DIAGRAM *167242* FIGURE 14: Wiring Diagram - Single Phase Johnson Controls Unitary Products...
  • Page 15: Wiring Diagram - Three Phase

    835964-UIM-A-0112 *412217* FIGURE 15: Wiring Diagram - Three Phase Johnson Controls Unitary Products...
  • Page 16 NOTES Subject to change without notice. Published in U.S.A. 835964-UIM-A-0112 Copyright © 2012 by Johnson Controls, Inc. All rights reserved. Supersedes: 414172-UIM-D-1211 Johnson Controls Unitary Products 5005 York Drive Norman, OK 73069...