Table 11: Air Balancing Wizard Points - York Sun Premier GZA1M Series Start-Up & Operation

Rooftop units
Table of Contents

Advertisement

Table 11: Air Balancing Wizard Points

Point
Air Balancing Mode
Unit Enable
Autozero Calibrate
Maximum Airflow
Economizer Damper % Command
Economizer Damper % Override
Mode
Economizer Damper % Override
Position
Fan % Command
Supply Fan % Override Mode
Supply Fan % Override Position
Fresh Air Intake Value
Fresh Air Intake Setpoint
Fresh Air Intake Max Sensor Range
Discharge Air Static Pressure
Duct Pressure Setpoint
Building Static Presssure
Building Pressure Setpoint
Supply Flow Value
Supply Pickup Gain
Supply Area
Altitude
SZVAV Cooling Min Fan Speed
SZVAV Heating Min Fan Speed
SZVAV Minimum Fan Speed
YORK
Supply Fan View
When the air balancer mode is set to enable, all other applicable points
are displayed in the view
This input will disable the unit if desired
This input forces an autozero now if desired. In order to complete an
autozero, set Unit Enable to disable and then wait 2 minutes before
attempting an autozero. This point auto resets to disable. After it switches
back to disable, Unit Enable can be set back to enable
This input is the design maximum airflow of the unit
This output is the current % output to the outside air damper
This input allows the outside air damper to be overridden. None = No
Override, Software = Position Override from user interface or MAP,
Hardware = Manually Override From Potentiometer on Analog Input. Set
back to none to release the override command
This input allows the outside air damper to be overridden to this adjusted
value when the outside air damper override mode point is set to software
This output is the current % output to the supply fan VFD. This point is
only displayed on this balancer view
This input allows the Supply Fan VFD command to be overridden. None
= No Override, Software = Position Override from user interface or MAP,
Hardware = Manually Override From Potentiometer on Analog Input.
Set back to none to release the override command. This point is only
displayed on this balancer view
This input allows the supply fan VFD command to be overridden to this
adjusted value when the supply fan output override mode point is set to
software. This point is only displayed on this balancer view
This input is the current outside airflow through the outside airflow station.
This input is the current outside airflow setpoint
This input is the current outside airflow maximum output value. Adjust this
in order to correct the current outside airflow reading
This input is the current discharge air static pressure reading
This input is the current duct static pressure setpoint
This input is the current building static pressure reading
This input is the current building static pressure setpoint
This input is the current discharge airflow reading. This value is calculated
using the piezometer and velocity pressure sensor on the inlet of the
supply fan
This input is the current discharge air VP sensor gain. This value can be
adjusted in order to correct the discharge airflow reading
This input is the area of the discharge air duct or fan cowling
This input is the current elevation. This is used for calculating the
discharge and return airflow
This input is the current minimum fan speed cooling setpoint. This
point is only viewable when the unit is configured as a SZVAV unit with
modulating or proportional heat
This input is the current minimum fan speed heating setpoint. This
point is only viewable when the unit is configured as a SZVAV unit with
modulating or proportional heat
This input is the current minimum fan speed setpoint. This point is only
viewable when the unit is NOT configured as a SZVAV unit with heating
Start-Up & Operation Guide | 5587001-YSG-A-520
Description
Writeable
Y
Y
Y
N
N
Y
Y
N
Y
Y
N
Y
Y
N
Y
N
Y
N
Y
Y
Y
Y
Y
Y
21