Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
H5-Starts
AV
H6-Runtime
AV
H6-Starts
AV
H7-Runtime
AV
H7-Starts
AV
H8-Runtime
AV
HE-T
AV
HighSpeedFan-
AV
MinPos
HRW-O
AV
HtgCapLim
AV
HtgDATLo-SP
AV
HtgDATUp-SP
AV
Hum-SP
AV
ModCompOut
AV
ModCondFan1Out
AV
ModCondFan2Out
AV
ModHtgOut
AV
OprHtgDAT-SP
AV
PFILT-DP
AV
RAD-O
AV
YORK
Object
Read/
Short Description
ID
Write
29983
R
H5-Starts
29985
R
H6-Runtime
29987
R
H6-Starts
29989
R
H7-Runtime
29991
R
H7-Starts
29993
R
H8-Runtime
30004
R
HE-T
HighSpeedFan-
30006
R/W
MinPos
30008
R
HRW-O
30010
R/W
HtgCapLim
30011
R/W
HtgDATLo-SP
30012
R/W
HtgDATUp-SP
30014
R/W
Hum-SP
30017
R
ModCompOut
30018
R
ModCondFan1Out
30019
R
ModCondFan2Out
30020
R
ModHtgOut
30021
R
OprHtgDAT-SP
30022
R
PFILT-DP
30025
R
RAD-O
Start-Up & Operation Guide | 5587001-YSG-A-520
Long
Point Definitions (Units)
Description
Heating Number
Displays the heating start counts for
Times ON 5
stage 5
Heating Stage
Displays the total runtime for stage 6
6 Accumulated
heating (hours)
Runtime
Heating Number
Displays the heating start counts for
Times ON 6
stage 6
Heating Stage
Displays the total runtime for stage 7
7 Accumulated
heating (hours)
Runtime
Heating Number
Displays the heating start counts for
Times ON 7
stage 7
Heating Stage
Displays the total runtime for stage 8
8 Accumulated
heating (hours)
Runtime
Heat Entering
Displays the active heat entering
Temperature
temperature (°F)
Economizer
A BAS command to adjust outside
Damper Minimum
air damper minimum position for high
Position High
speed fan (0–100%)
Speed Fan
Heat Recovery
Displays the ERW control output (%)
Wheel Output
Heating Capacity
A BAS command to adjust the
Limit
heating capacity limit (0–100%)
Heating DAT
A BAS command to adjust heating
Lower Setpoint
DAT lower setpoint (85.0–134.0°F)
Heating DAT
A BAS command to adjust heating
Upper Setpoint
DAT upper setpoint (85.0–134.0°F)
Humidification
A BAS command to adjust
Setpoint
humidification setpoint (0–100 %RH)
Modulating
Displays the active modulating
Compressor
compressor value (0–100%)
Output
Modulating
Displays the active modulating
Condenser Fan 1
condenser fan 1 value (0–100%)
Output
Modulating
Displays the active modulating
Condenser Fan 2
condenser fan 2 value (0–100%)
Output
Modulating Heat
Displays the active modulating heat
Output
value (0–100%)
Operating Heating
Displays the active heating DAT
DAT Setpoint
setpoint (°F)
Pre-Filter
Displays the differential pressure for
Differential
first filters (pre-evap) (iwg)
Pressure
Return Air
Displays the status of return air
Damper
damper command (%)
Command
105