York Sun Premier GZA1M Series Start-Up & Operation page 90

Rooftop units
Table of Contents

Advertisement

5587001-YSG-A-520 | Start-Up & Operation Guide
Table 26: Menus and Submenus (Continued)
Menu
Submenu
Start-Up
Wizard (Refer
Start-Up
to Start-
Wizard
Up Wizard
(Figure 33)
Sequence on
page 26)
90
Parameters Displayed / Default
Start-Up Wizard Status
Active Test Status
Self Test Time Remaining
Self Test Time Remaining
Phase A Voltage
Phase B Voltage
Phase C Voltage
Supply Fan L1 Amps
Supply Fan L2 Amps
Supply Fan L3 Amps
Liquid Temperature
Liquid Pressure
Suction Temperature
Suction Pressure
Check OK?
Continue
Damper Test / Disable
Heat Recovery Wheel Test / Disable
Supply Fan Test / Disable
Compressor Test / Disable
Heating Test / Disable
Run Startup Wizard / No
Cancel
Conditions for Parameters Displayed
Units / Range
OFF, Enter Supply Line Voltage, OA and RA Dampers
Half Open, OA and RA to Outside Air Only, OA and
RA Damper Test Done, Exhaust Damper Half Open,
Exhaust Damper Fully Opening, Exhaust Damper
Fully Closing, Exhaust Damper Test Done, Isolation
Damper Fully Opening, Isolation Damper Fully
Closing, Isolation Damper Test Done, Heat Recovery
Dampers Open, Heat Recovery Dampers Close,
Heat Recovery Wheel On, Heat Recovery Wheel
On Max, Heat Recovery Test Done, Supply Fan on
Max, Supply Fan Duct Pressure Control, Supply
Fan Test Done, Compressor 1A Test, Compressor
1B Test, Compressor 2A Test, Compressor 2B Test,
Check Compressor 1A Oil, Check Compressor 1B Oil,
Check Compressor 2A Oil, Check Compressor 2B
Oil, Charge Check Circuit 1, Charge Check Circuit 2,
Compressor 1A Test Done, Compressor 1B Test Done,
Compressor 2A Test Done, Compressor 2B Test
Done, Unavailable for Charge Check, Enter Circuit 1
Data, Enter Circuit 2 Data, Circuit 1 Tests Done, Circuit
2 Tests Done, Compressor Tests Done, Electric Heat
1–8 Test Done, Verify Electric Heat 1–8 On, Gas Heat
1–5 Low Fire Start, Gas Heat 1–5 High Fire Start,
Verify Gas Heat 1–5 Low Fire, Verify Gas Heat 1–5
High Fire, Gas Heat Module 1–5 Test Done, Gas Heat
Module 1–5 Cool Down, Heating Tests Done
Stabilize, Wait, Check, Available, Not Run, Pass,
Warning-Low DSP, Warning-SAT Not Dropped,
Warning-SAT Not Increased, Warning-BSP Not
Dropped, Warning, Fail-APS On Early, Fail-APS Off,
Fail-Low Voltage, Fail-Low DSP, Fail-HPS, Fail-FRZ,
Fail-LPS, Fail-LS, Fail-GV Off, Fail-Damper, Fail-
SAT Unreliable, Fail-VFD Fault, Fail- Fan Overload,
Fail, Fail-DSP Unreliable, Fail-BSP Unreliable
seconds
seconds
V
V
V
A
A
A
deg F (-50 to 500)
psi (-50 to 750)
deg F (-50 to 500)
psi (-50 to 750)
No, Yes
No, Yes
Disable, Enable
Disable, Enable
Disable, Enable
Disable, Enable
Disable, Enable
No, Yes
No, Yes
YORK