Fire Safety Requirements - Juniper Junos Space JA2500 Hardware Manual

Hide thumbs Also See for Junos Space JA2500:
Table of Contents

Advertisement

JA2500 Junos Space Appliance Hardware Guide
Related
Documentation

Fire Safety Requirements

116
Varning! Denna varningssymbol signalerar fara. Du befinner dig i en situation
som kan leda till personskada. Innan du utför arbete på någon utrustning
måste du vara medveten om farorna med elkretsar och känna till vanligt
förfarande för att förebygga skador.
General Safety Guidelines and Warnings on page 113
Grounded Equipment Warning on page 131
Installation Instructions Warning on page 125
Laser and LED Safety Guidelines and Warnings for Junos Space Appliances on page 119
Maintenance and Operational Safety Guidelines and Warnings on page 131
Warning Statement for Norway and Sweden on page 118
This topic applies to the following Junos Space Appliances: JA1500 and JA2500.
In the event of a fire emergency involving appliances and other network equipment, the
safety of people is the primary concern. You should establish procedures for protecting
people in the event of a fire emergency, provide safety training, and properly provision
fire-control equipment and fire extinguishers.
In addition, you should establish procedures to protect your equipment in the event of a
fire emergency. Juniper Networks products should be installed in an environment suitable
for electronic equipment. We recommend that fire suppression equipment be available
in the event of a fire in the vicinity of the equipment and that all local fire, safety, and
electrical codes and ordinances be observed when you install and operate your equipment.
Fire Suppression
In the event of an electrical hazard or an electrical fire, you should first turn power off to
the equipment at the source. Then use a Type C fire extinguisher, which uses noncorrosive
fire retardants, to extinguish the fire.
Fire Suppression Equipment
Type C fire extinguishers, which use noncorrosive fire retardants such as carbon dioxide
and Halotron™, are most effective for suppressing electrical fires. Type C fire extinguishers
displace oxygen from the point of combustion to eliminate the fire. For extinguishing fire
on or around equipment that draws air from the environment for cooling, you should use
this type of inert oxygen displacement extinguisher instead of an extinguisher that leaves
residues on equipment.
Do not use multipurpose Type ABC chemical fire extinguishers (dry chemical fire
extinguishers). The primary ingredient in these fire extinguishers is monoammonium
phosphate, which is very sticky and difficult to clean. In addition, in the presence of minute
Copyright © 2014, Juniper Networks, Inc.