Pentax DSI-200 Series User Manual page 92

Advertisement

Set
Function
value
settings
Motor speed
13
Output current
14
output voltage
15
Output torque (actual
16
P5-09
When the HDO terminal is selected as a pulse output, the function code is used to select
the maximum frequency value of the output pulse.
P5-10
P5-11
The above function codes are generally used to correct the zero drift of the analog output
and the deviation of the output amplitude. It can also be used to customize the desired AO
output curve.
If the zero is denoted by "b", the gain is denoted by k, the actual output is denoted by Y,
and the standard output is denoted by X, then the actual output is: Y = kX + b.
Among them, AO1, AO2 zero partial coefficient of 100% corresponds to 10V (or 20mA),
the standard output is no zero bias and gain correction, the output 0V ~ 10V (or 0mA ~
20mA) corresponding to the amount of analog output.
For example, if the analog output content is the operating frequency, it is desirable to
output 8V when the frequency is 0 and 3V when the frequency is the maximum frequency.
The gain should be set to "-0.50" and the zero bias should be set to "80%".
P5-17
Relay 1 outputs the delay
P5-18
Set the output terminal HDY, relay 1, relay 2, from the state change to the actual output to
produce changes in the delay time
P5-22
Pulse or analog output 0.0% to 100.0% of the
0~The maximum output frequency corresponds
-2 times the motor rated torque~2 times the motor
value)
rated torque
HDP output max
frequency
Set range
AO1 Zero partial
coefficient
Set range
AO1 profits
Set range
HDY output the delay
time
Set range
time
Set range
HDO Output terminal
valid status selection
corresponding function
to the speed
0.0A~1000.0A
0.0V~1000.0V
Factory default
0.01kHz~100.00kHz
Factory default
-100.0%~+100.0%
Factory default
-10.00~+10.00
Factory setting
0.0s~3600.0s
Factory setting
0.0s~3600.0s
Factory default
- 92 -
50.00kHz
0.0%
1.00
0.0s
0.0s
00000