Group
Description
Pd-00
This parameter is used to set transmission speed between host
computer and AC drive. Note that baud rate of host computer must
be the same as that of AC drive. Otherwise, communication shall
fail. The higher baud rate is, the faster communication will be.
Modbus Data
format
Pd-01
Set range
Note that data format of host computer must be the same as that of
AC drive. Otherwise, communication shall fail.
Local address
Pd-02
Set range
This parameter is used to set address of AC drive. This address is
unique (except broadcast address), which is basis for point-to-
point communication between host computer and AC drive. When
Pd
Communication
Baud rate
Set range
Factory default
0: No check <8,N,2>
1: Even parity check <8,E,1>
2: Odd parity check <8,O,1>
3: No check, data format <8,N,1>
Factory default
164
Parameter
Factory default
Bit:MODBUS Baud rate
0:300BPS
1:600BPS
2:1200BPS
3:2400BPS
4:4800BPS
1~247,0 Broadcast address
6005
5:9600BPS
6:19200BPS
7:38400BPS
8:57600BPS
9:115200BPS
0
1