Lower frequency
37
arrival
(Shutdown also output)
38
Warning output
Motor over
39
temperature alarm
40
The run time arrives
41
Fault output
HDP Output function selection(Pulse
P5-06
P5-07
AO1 Output function selection
HDP terminal output pulse frequency range of 0.01 KHz ~ P5-09 (HDO output maximum
frequency), P5-09 can be set between 0.01 kHz ~ 100.00 kHz.
Analog output AO1 and AO2 output range of 0V ~ 10V, or 0mA ~ 20mA.
Pulse output or analog output range, and the corresponding function of the scaling
relationship as shown in the following table:
Set
Function
value
Working frequency
0
Set frequency
1
Output current
2
Output torque
3
(Absolute value)
Output power
4
Output voltage
5
High speed pulse
6
7
8
9
Length
10
Number setting
11
Communication
12
When the operating frequency reaches the lower
limit frequency, the ON signal is output. The signal is
also ON in the shutdown state
When the inverter fails, and the fault processing
mode for the continued operation, the inverter alarm
output.
When the motor temperature reaches P9-58 (motor
overheat pre-alarm threshold), the ON signal is
output. (Motor temperature can be viewed by d0-34)
When the inverter starts running for more than the
time set by P8-53, the ON signal is output.
Fault output (for freewheel failure and undervoltage
is not output)
output terminal)
Pulse or analog output 0.0% to 100.0% of the
input
AI1
AI2
AI3
Factory
default
Factory
default
corresponding function
0~max output frequency
0~max output frequency
0~2 times motor rated current
0~2 times rated Output torque
0~2 times rated power
0~1.2times AC drive output voltage
0.01kHz~100.00kHz
0V~10V
0V~10V(or 0~20mA)
0V~10V
0~max set length
0~ max number
0.0%~100.0%
- 91 -
0
0