Figure 6-27 shows the function of the PID initial value
PID Integral attribute
PA-25
Set range
Integral separation
If the integral separation is valid, when the multi-function digital S integral is suspended
(function 22) is valid, the integral PID integral of the PID stops operation, and PID is only
proportional and differential.
When the integral separation selection is invalid, the integral separation is invalid
regardless of whether the multi-function digital S is valid or not.
Whether to stop the points after outputting the limit:
After the PID operation output reaches the maximum or minimum value, you can choose
whether to stop the integration effect. If the stop is selected, the PID integral stops
counting at this time, which may help to reduce the overshoot of the PID.
PID Feedback loss detection
PA-26
Set range
PID Feedback loss test value
PA-27
Set range
This function code is used to determine if PID feedback is lost.
When the PID feedback is less than the feedback loss detection value PA-26 and the
duration exceeds the PID feedback loss detection time PA-27, the inverter alarm fault
FU31 is processed and processed according to the selected fault handling method.
Factory default
Bit
0: invalid
Ten
0: Continue to score
value
0.0%:Do not judge feedback loss
Whether to stop the integration after
outputting the limit value
Factory
default
0.1%~100.0%
Factory
default
0.0s~20.0s
- 119 -
00
Integral separation
1: valid
1: stop to score
0.0%
0.0s