Pentax DSI-200 Series User Manual page 102

Advertisement

Accumulative power-on time
P8-16
Setting Range
Multi-function digital terminal HDO output ON signal when accumulative power-on time
of the AC drive (P7-13) exceeds value set in FP-16.
Set the cumulative time to reach 100 hours: P8-16 = 100.
Then, when the accumulated power time reaches 100 hours, the inverter output faulty of
FU29.
Accumulative running time
P8-17
Setting Range
This parameter is used to set up the running time of the inverter.
When the cumulative running time (P7-09) arrives at the set running time, the multi-
function digital terminal HDO output ON signal.
Start-up terminal protection
P8-18
Setting Range
This parameter relates to the safety protection of the frequency inverter.
If the parameter is set to 1, if the inverter is powered on and run command is valid(such as
terminal with the run command close before electricity ), the frequency inverter does not
respond to run command, you must firstly remove run command one time, after run
command is valid again, frequency inverter will response run command.
In addition, if the parameter is set to 1, if the frequency inverter fault reset and run
command is valid, the frequency inverter also does not respond run command, you must
firstly remove run command to avoid running protection state.
Setting this parameter to 1 can prevent the motor from responding run command and
becoming dangerous in the event of electrifying or failure reset when do not know all
situation.
Frequency detection value FDT1
P8-19
Setting Range
Frequency detection hysteresis
P8-20
Setting Range
When running frequency exceeds the detection value, the multi-function digital terminal
HDO output ON signal.
When the running frequency is lower than the detection value, HDO output OFF signal.
The above parameters are used to set the detection value of the output frequency and the
lag value of the output action end. P8-20 is the percentage of the lag frequency relative to
the frequency detection value P8-19. Figure 6-16 show FDT function.
threshold
threshold
selection
0:no protection
(FDT1)
FGT1
Factory default
0h~65000h
Factory default
0h~65000h
Factory default
Factory default
0.00Hz~max. frequency
Factory default
0.0%~100.0%(FDT1 level)
- 102 -
0h
0h
0
1: protection
50.00Hz
5.0%