dO-32
Viewing any register address value
dO-34
Motor temperature
dO-35
Target torque
dO-36
Resolver position
6. Parameter Description
Function
code
P0-01:
1st motor
speed
control
mode
Main frequency
source A selection
P0-03
Description
Set 0:non-speed
Sensor vector control
(SVC)
Set 1:with speed
Sensor vector control
(FVC)
Set 2:V/F control
(speed degree open
loop control)
(Factory default)
Factory default
0: digital setting (preset frequency P0-08, UP / DOWN
can be modified, power is not memory)
1: digital setting (preset frequency P0-08, UP / DOWN
can be modified, power-down memory)
Set range
2: AI1 (J6 jumper)
5: High-speed pulse setting (S5)
6: Multi-step command
7: PLC
Application
Refers to open loop vector control, suitable for
the usual high-performance control occasions, a
drive can only drive a motor. Such as machine
tools, centrifuges, drawing machines, injection
molding machines and other loads.
Refers to the closed-loop vector control, the
motor must be installed encoder, the inverter
must be the same type of adapter with the PG
card. Suitable for high-precision speed control or
torque control of the occasion. A drive can only
drive one motor. Such as high-speed paper
making machinery, lifting machinery, elevators
and other loads.
Applicable to the load requirements are not high,
or a drive drag multiple motor occasions, such as
fans, pump load. Can be used for a drive drag
more than one motor occasions.
3: AI2
8: PID
9: Communication
- 59 -
0.01Hz
1
1℃
0.1%
2
4: AI3
701FH
7020H
7022H
7023H