Initial notification of critical alerts will pop up on the home screen and will be listed under notification menu. Minor and moderate alerts are found only under the notification menu.
Moderate alerts are not emailed to Homeowners. Dealers will get an email and code can be seen on thermostat under the installer notification section.
Applicable
Alert
Priority
System
Code
Condition
Component(s)
132
Critical
Thermostat
180
Critical
Smart Hub
310
Moderate
Smart Hub
344
Critical
Furnace
345
Critical
Thermostat
Table 16. Alert Codes and Troubleshooting
Actual
Displayed
Component or System Operational State and Troubleshooting Tip
Alert Text
• System component control software is corrupted.
• Recycle power.
Failed Flash CRC
• If failure re-occurs, replace the system component control.
Check
Manual system power reset is required to recover from this alert code.
• The thermostat has found a problem with a system component's outdoor temperature sensor. In normal operation after system
component control recognizes sensors, the alarm will be sent if valid temperature reading is lost.
• Compare outdoor sensor resistance to temperature / resistance charts in unit installation instructions.
Outdoor
• Replace sensors pack if necessary.
Temperature
• At the beginning of (any) configuration, furnace, air-handler control or equipment interface module will detect the presence of the
Sensor Problem
sensor(s).
• If detected (reading in range), appropriate feature will be set as 'installed' and shown in the 'About' screen.
Automatically clears upon configuration, or sensing normal values.
• There is a discharge air temperature sensor issue.
• Compare discharge temperature sensor (DATS) resistance to temperature / resistance charts in system component installation
instruction.
• Replace discharge air sensor if necessary.
Discharge Air Temp
Sensor Problem
• Confirm there is no short or open circuits in the iComfort thermostat connections to any of the other components in the
communication system.
• Issues with a DATS connected to smart hub not generate an alert code.
Automatically clears 30 seconds after condition is detected as recovered or after system restart.
• Link Relay Problem. Relay Y1 Failure
• Possible Y1 relay failure.
Relay Y1 Stuck
• All system operations will stop.
Automatically clears five minutes after Y1 input sensed OFF.
• The O relay on the system component has failed. Either the pilot relay contacts did not close or the relay coil did not energize.
• Possible O relay / stage 1 failure.
• Pilot relay contacts did not close or the relay coil did not energize.
Relay O Failure
• Replace system component (device) control.
Automatically clears after the fault recovered following reset.