Lennox iComfort E30 Installation And Setup Manual page 21

Smart thermostat
Hide thumbs Also See for iComfort E30:
Table of Contents

Advertisement

Parameter
Description
(In alphabetical
order)
Options are Maximum Overcooling, Midpoint Overcooling and Minimum Overcooling. Default is Maximum Overcooling.
Maximum Overcooling: Indoor temperature > (greater than) two degrees above heating setpoint.
Humiditrol Comfort
Midpoint Overcooling: Indoor temperature > (greater than) HEAT setpoint + COOL setpoint / 2.
Adjust
Minimum Overcooling: Indoor temperature > (greater than) two degrees below cooling setpoint.
XP20 and XP25 is not compatible with Humiditrol (EDA).
Range is -10.0 to 10.0%. Default is 0.0%.
Humidity Reading
If it is determine that the actual humidity percentage being detected at the thermostat is off based on independent readings using other humidity reading devices, the
Calibration
display can be adjusted using this setting.
Lock In 2nd Stage
HP by Outdoor
This accessory allows the unit to lock in 2nd stage HP heating when the outdoor temperature goes below the jumper pin setting.
Temp
Options are off, 40°F, 45°F, 50°F and 55°F (4°C, 7°C, 10°C and 13°C). Default is off.
(Lennox Two-Stage
Heat Pumps Only)
The highest temperature setting that the heat set point can be set on the thermostat. Default is 90.0F (32.33°C). Range is 60.0 to 90.0°F (15.56 to 32.22°C). Adjustable
Max Heat Setpoint
in increments of 1°F (0.56°C).
Max Humidification
Maximum allowed set point for humidification.
Setpoint
Range is 15 to 45%. Default is 45%. Adjustments are in increments of 1%.
The lowest temperature setting that the cool set point can be set on the thermostat. Range is Range is 60.0 to 90.0°F (15.56 to 32.22°C). Default is 60°F (15.56°C).
Min Cool Setpoint
Adjustments are in increments of 1°F (0.56°C).
Min
Adjustable minimum dehumidification setting.
Dehumidification
Range is 40 to 60%. Default is 40%. Adjustments are in increments of 1%.
Setpoint
Outdoor
Temperature
Range is -10 to 10°F (-5.56 to 5.56°C). Default is 0°F (0.0°C). Adjustments are in increments of 1°F. (0.56°C) This will allow for adjustment to the outdoor temperature
Reading
display when the display temperature is off. Outdoor sensor is required.
Calibration
Reset smart hub
Reset smart hub (erases smart hub settings and restarts installer setup).
Severe Weather Protection
Options are enabled or disabled. Default is disabled. When enabled either the heat or freezing alert temperature setting will automatically generate a email notification to the homeowner that the
applicable condition exist and homeowner interaction is required.
Notification is dependent on the thermostat having a active Wi-Fi connection and the user account has been setup and includes a valid email address.
This will notified the homeowner when the indoor temperature reaches the setting defined for this parameter. Range is 80°F to 100°F (26.67 to 37.78°C) with a factory default of 90°F (32.22°C).
Increments adjusted by 1.0°F (0.56°C).
This will notified the homeowner when the indoor temperature reaches the setting defined for this parameter. Range is 30°F to 50°F (-1.11 to 10.0°C) with a factory default of 40°F 4.4°C).
Increments adjusted by 1.0°F (0.56°C).
Table 7. Smart Hub Parameters
Heat Alert Temperature
Freezing Alert Temperature
21