Can increase or decrease the number of electric elements to come on during a call for defrost. Thermostat will have a demand for heat.)
During Defrost
Range is 0 to 5 electric heat stages. Default is 2. Adjustments are in increments of 1.
A unique name can be assigned to this component. Name can be up to 29 characters. Name can consist of letters, numbers, special characters and spaces. Default
Equipment Name
name is Subnet Controller.
Default Group ID is 1. Valid range is 0 to 9.
Multiple smart hubs in a home can be assigned to a group (up to nine groups with up to eight smart hubs in each group). All smart hubs in a group can communicate
Group ID
with other smart hubs in the same group over the home Wi-Fi network.
If a smart hub is set to Group ID 0, there is no connectivity with another smart hub.
Heat Cool Stages Locked In
Heat Cool (H/C) Stages Lock in default is disabled (heat/cool stages are turned off separately). If changed to Enabled, heat/cool stages are turned off together. For non-variable speed systems
only.
Table 7. Smart Hub Parameters
Cooling (1- and 2-Stages)
H/C
1st stage
Stages
OFF
Stg1 Differential
Locked =
Disabled
2nd stage
OFF
H/C
1st stage
Stages
OFF
Stg1 Differential
Locked =
2nd stage
Enabled
OFF
SP -1.5
SP -1.0
SP -0.5
POINTS:
Heating - Non-Heat Pump or Heat Pump w/o backup heat - 1 or 2 stages