G9Sr-Ad□-□ In E-Stop Application Up To Pld - Omron G9SR Series Operation Manual

Safety relays
Hide thumbs Also See for G9SR Series:
Table of Contents

Advertisement

Operation manual
11.2.2
G9SR-AD□-□ in E-Stop application up to PLd
Settings G9SR-AD:
Manual Restart enabled
EDM enabled
Dynamic Input Test disabled
Dip switch settings:
Description:
E-Stop pushbutton connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Feedback loop (EDM) connected to T32
Remarks:
This setup can also be used with safety limit switches and key operated door switches.
For door and gate monitoring applications please consider the requirements from ISO
14119.
Wiring is using the dynamic test pulses.
Applicable up to PLd acc. EN ISO 13849-1 (electrical system).
Motor circuit (contacts of KM1 and KM2) not shown.