Omron G3PJ Series Manual

Omron G3PJ Series Manual

Solid state relays for heaters

Advertisement

Solid State Relays for Heaters
G3PJ
Single-phase SSR for low heat
generation enables carrying 25 A * even
for close mounting of three SSRs to
contribute to downsizing of control
panels.
Models available with push-in plus input
terminals.
* G3PJ-@25B(-PU)
• SCCR of 10kA (UL 508).
• Surge pass protection improved surge dielectric strength for
output currents. (OMRON testing)
• Both push in plus and screw Technology input terminals
available.
• Mount to DIN Track or with screws.
• Conforms to cULus and EN standards (TÜV certification).
• RoHS compliant.
Refer to Safety Precautions on page 5.
Model Number Structure
Model Number Legend
@ @@B - @ DC12-24
G3PJ
-
1
2
Basic Model Name
1. Rated Load Voltage
2: 24 to 240 VAC
5: 100 to 480 VAC
Ordering Information
Input
Output
Insulation
terminal
terminal
method
Screw
terminals
Screw
Phototriac
terminals
coupler
Push-in
plus
technology
* The applicable load current depends on the ambient temperature. For details, refer to Load Current vs. Ambient Temperature in Engineering
Data on page 3.
3
Rated input voltage
2. Rated Load Current for Three Close-mounted SSRs
15: 15 A
25: 25 A
Operation
Rated input
Zero cross
indicator
voltage
function
Yes (orange)
12 to 24 VDC
Yes
For the recent information on models that have been certified
for safety standards, refer to your OMRON website.
3. Input Terminal Form
Blank: Screw technology
PU: Push-in plus technology
Rated load current (ambient
temperature of 40°C) *
Rated load
voltage
Close mounting
(Three SSRs)
15 A
24 to 240 VAC
25 A
15 A
100 to 480 VAC
25 A
15 A
24 to 240 VAC
25 A
15 A
100 to 480 VAC
25 A
Model
Separate
mounting
18 A
G3PJ-215B DC12-24
27 A
G3PJ-225B DC12-24
23 A
G3PJ-515B DC12-24
27 A
G3PJ-525B DC12-24
18 A
G3PJ-215B-PU DC12-24
27 A
G3PJ-225B-PU DC12-24
23 A
G3PJ-515B-PU DC12-24
27 A
G3PJ-525B-PU DC12-24
1

Advertisement

Table of Contents
loading

Summary of Contents for Omron G3PJ Series

  • Page 1 (OMRON testing) • Both push in plus and screw Technology input terminals For the recent information on models that have been certified for safety standards, refer to your OMRON website. available. • Mount to DIN Track or with screws.
  • Page 2: Specifications Ratings

    G3PJ Specifications Ratings Input (at an Ambient Temperature of 25°C) Item Operating voltage Must operate Must release Rated voltage Current Model range voltage voltage G3PJ-2@@B(-PU)/ 12 to 24 VDC 9.6 to 30 VDC 7 mA max. 9.6 VDC max. 1.0 VDC min. G3PJ-5@@B(-PU) Output Item...
  • Page 3: Engineering Data

    G3PJ Engineering Data Input Voltage vs. Input Impedance and Input Voltage vs. Input Current G3PJ-2@@B(-PU) G3PJ-5@@B(-PU) Ta = 25°C Ta = 25°C Input current Input current Input impedance Input impedance Input voltage (V) Input voltage (V) Load Current vs. Ambient Temperature G3PJ-215B(-PU), G3PJ-225B(-PU) G3PJ-515B(-PU), G3PJ-525B(-PU) Close Mounting of Three SSRs...
  • Page 4 G3PJ Dimensions (Unit: mm) Solid State Relays SSRs with Screw Terminals G3PJ-215B ±0.2 G3PJ-225B Two, 4.6 dia. G3PJ-515B Two, G3PJ-525B M3.5 ±0.2 100 max. Two, M4 4.6 × 5.6 Oval hole 22.5 max. Note: Without terminal cover. Note: With terminal cover. Mounting Holes Terminal Arrangement/Internal Circuit Diagram ±0.3...
  • Page 5: Safety Precautions

    Precautions for Safe Use CAUTION which, if not avoided, may result in minor or moderate injury or in property damage. OMRON constantly strives to improve quality and reliability. The G3PJ, however, use semiconductors, and semiconductors may Indicates supplementary comments on Precautions for commonly malfunction or fail.
  • Page 6 G3PJ Installation and Mounting Installation and Usage • Mount the G3PJ in the specified direction. (Refer to Mounting on • Do not apply a voltage or current that exceeds the rating to any page 7.) Excessive heat generated by the G3PJ may cause short- terminal.
  • Page 7 G3PJ Mounting Push-in plus technology • The G3PJ is heavy. Firmly mount the DIN Track and secure both 1. Connecting Wires to the Push-in plus technology ends with End Plates for DIN Track mounting models. When Part Names of the technology mounting the G3PJ directly to a panel, firmly secure it to the panel.
  • Page 8 10 to 15˚ 0.4 mm 2.5 mm 2. With the flat-blade screwdriver still inserted into the release hole, Model Manufacturer remove the wire from the terminal insertion hole. XW4Z-00B Omron ESD 0.40✕2.5 Wera SZF 0.4✕2.5 Phoenix Contact 0.4✕2.5✕75 302 Wiha AEF.2.5✕75...
  • Page 9 G3PJ Relationship between the G3PJ and Ducts or Other This is a Class A product (for industrial environments). In a domestic Objects Blocking Airflow environment, the G3PJ may cause radio interference, in which case Incorrect Example Countermeasure 1 Countermeasure 2 the user may be required to take appropriate measures.
  • Page 10 MEMO...
  • Page 11: Terms And Conditions Agreement

    Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it to actual application requirements.
  • Page 12 The Netherlands Hoffman Estates, IL 60169 U.S.A. Tel: (31)2356-81-300/Fax: (31)2356-81-388 Tel: (1) 847-843-7900/Fax: (1) 847-843-7787 © OMRON Corporation 2016 All Rights Reserved. OMRON (CHINA) CO., LTD. OMRON ASIA PACIFIC PTE. LTD. In the interest of product improvement, Room 2211, Bank of China Tower, No.

Table of Contents