Operation manual
7.3
Dip switches and functions of G9SR-AD□-□
The DIP-Switches are used to configure the G9SR-AD unit for the
application.
There are two banks of DIP-switches in the G9SR-AD.
Both DIP-switch banks have eight switches.
To select a function, the switches on both DIP-switch banks
have to be set identically.
Example:
DIP SWITCH 3, BANK1 = "OFF"
and
DIP SWITCH 3, BANK2 = "OFF" => OK
DIP SWITCH 3, BANK1 = "OFF"
and
DIP SWITCH 3, BANK2 = "ON" => ERROR
!
Caution
Use the switches to configure following functions:
Function
Restart
Dynamic Input Testing
EDM
INPUT LOOP
OUTPUT LOOP
Do not change the setting of the DIP switches during operation of
the G9SR-AD. In this case, the G9SR-AD will change the outputs
to "OFF" and will enter a lockout state.
Switch
G9SR-AD□-□
1
ON =
OFF =
2
ON =
OFF =
3
ON =
OFF =
4/5
OFF/OFF = No G9SR-BC□-□ connected
OFF/ON = Setting not allowed
ON/OFF = 1 G9SR-BC□-□ connected
ON/ON =
6/7
OFF/OFF = No G9SR-EX□-T90-□ connected
OFF/ON = 1 G9SR-EX□-T90-□ connected
ON/OFF = 2 G9SR-EX□-T90-□ connected
ON/ON =
8
Reserved
Auto restart
Manual restart
Enabled
Disabled
Enabled
Disabled
2 G9SR-BC□-□ connected
3 G9SR-EX□-T90-□ connected
G9SR
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
Page 27 of 79