G9Sr-Bc□-□ For Door Interlocking Up To Pld With F3S-Tgr-N__C - Omron G9SR Series Operation Manual

Safety relays
Hide thumbs Also See for G9SR Series:
Table of Contents

Advertisement

Operation manual
11.1.4
G9SR-BC□-□ for door interlocking up to PLd with F3S-TGR-N__C
Settings G9SR-BC:
Manual Restart enabled
EDM enabled
Dynamic Input Test disabled
Aux inverted
Dip switch settings:
Description:
Non-contact switch connected to T12 and T22
Restart pushbutton connected to T31
KM1 and KM2: Motor Contactors
Feedback loop (EDM) connected to T32
Remarks:
This setup can also be used with safety limit switches and key operated door switches.
For door and gate monitoring applications please consider the requirements from ISO
14119.
Applicable up to PLd acc. EN ISO 13849-1 (electrical system).
Motor circuit (contacts of KM1 and KM2) not shown.
Page 58 of 79