8.3
Rotary switch functions of G9SR-EX□-T90-□
The rotary switches are used to configure the G9SR-EX for the application.
The OFF- and ON-delay time can be set independently.
!
Caution
There are four rotary switches in the G9SR-EX to configure the ON- and OFF-delay
time setting. Switch 1 and 3 define the ON-delay time setting. Switch 2 and 4 define the
OFF-delay time setting.
The rotary switch settings represent following time delays:
0
1
2
0s
0.1s
0.2s
8
9
A
5s
10s
20s
8.3.1

ON-delay

To select an ON-delay time, use switch 1 and switch 3. They have to be set identically
for a valid ON-delay time setting.
8.3.2

OFF-delay

To select an OFF-delay time, use switch 2 and switch 4. They have to be set identically
for a valid OFF-delay time setting.
Page 34 of 79
Do not change the setting of the switches during
operation of the G9SR-EX. In this case, the G9SR-EX
will change the outputs to "OFF" and will enter a
lockout state.
3
4
0.5s
1s
B
C
30s
45s
5
6
7
1.5s
2s
2.5s
D
E
F
60s
75s
90s