F040

Automatic Function Selection

Program ⇒ Utilities ⇒ Display Parameters
This parameter setting is used to configure multiple parameters with the setting
of only one parameter. From the selection below multiple parameters may be
set as indicated in the table.
Once set, the selected configuration is placed in effect and remains in effect
until this parameter is changed or the individual settings are changed.
Set this parameter to Disable to set these parameters individually.
Note:
After performing the desired selection the EOI display returns to
Disabled though the selected function has been carried out (i.e.,
without this, if selection 1 is performed, F004 and F207 would
hold the RR terminal setting regardless of attempts to change the
settings individually).
Settings:
0 — Disabled
1 — RR
2 — V/I
3 — RR or V/I Switched via Terminal Board
4 — Keypad = Frequency/Terminal Board = Command
5 — Keypad = Frequency and Command
Related
Default
0-Disable 1-RR 2-V/I
Parameters
Settings
CMOD
Terminal
F003
Board
FMOD1
RR
N/C
F004
S3 Terminal
Preset
F117
Speed 3
Freq.
Terminal
Priority
N/C
Board
F200
V/I Setup
0.0%
F201
FMOD2
V/I
N/C
F207
N/C = No Change — the setting remains as it was before setting parameter F040.
H9 ASD Installation and Operation Manual
User Settings
3-RR or V/I
via TB
N/C
RR
N/C
RR
Freq. Ref.
N/C
Priority
Terminal Board
N/C
20.0%
RR
V/I
Direct Access Number — F040
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
4-Keypad/
5-Keypad
Freq.
Freq/CMD
CMD/TB
Terminal
Keypad
Board
Keypad
N/C
N/C
Keypad
F040
85