Toshiba H9 Installation And Operation Manual page 253

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

Input
Function
Function Name
Command
0
NOP (No Operation)
1
ST
2
STN
3
AND
4
ANDN
5
OR
6
ORN
7
EQ
8
NE
9
GT
10
GE
11
LT
12
LE
13
ASUB
14
ON (Timer)
15
OFF (Timer)
16
COUNT1 (Timer)
17
COUNT2 (Timer)
18
HOLD
19
SET
20
RESET
H9 ASD Installation and Operation Manual
Table 11. My Function Operator selections.
My Function Computational Selections
Disables the My Function feature.
Execute data read/transfer.
Execute inverted data read/transfer.
Logical product of A AND B.
Logical product of A AND B.
Logical sum of A OR B.
Logical sum of A OR B.
Compares data — Outputs 1 if Equal; 0 if not Equal.
Compares data — Outputs 0 if Equal; 1 if not Equal.
Compares data — Outputs 1 if A>B; 0 if A≤B.
Compares data — Outputs 1 if A≥B; 0 if A<B.
Compares data — Outputs 1 if A<B; 0 if A≥B.
Compares data — Outputs 1 if A≤B; 0 if A>B.
Outputs absolute difference between A and B — |A–B|
Enables the On response time delay settings of My Function Time Data 1 – 5
(F928
– F932) for My Function Data.
Enables the Off response time delay settings of My Function Time Data 1 – 5
(F928
– F932) for My Function Data.
Outputs a 1 upon reaching the pulse count setting of F933.
Outputs a 1 upon reaching the pulse count setting of F934.
Outputs the peak output value since powering up or since the last reset.
Sets data.
Resets data.
Function Description
245

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents