F416

Stall Prevention Factor 1

Program ⇒ Protection ⇒ Stall
This parameter is to be adjusted in the event that the motor stalls when operated
above the base frequency.
If a momentary heavy load occurs the motor may stall before the load current
reaches the stall prevention level setting of F601.
A drop in the supply voltage may cause fluctuations of the load current or may
cause motor vibration. A gradual adjustment of this parameter may alleviate
this condition.
Start with a setting of 85 at these parameters and gradually adjust them from
there one at a time until the desired results are produced.
Adjustments to this parameter may increase the load current of the motor and
subsequently warrant an adjustment at the Motor Overload Protection Level
setting.

Torque Command Selection

Program ⇒ Torque ⇒ Torque Control
When operating in the Torque Control mode, this parameter allows the user to
select the source of the torque command signal.
Settings:
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 2-wire
6 — RS485 4-wire
7 — Communication Option Board
8 — RX2 Option (AI1)

Tension Torque Bias Input

Program ⇒ Torque ⇒ Torque Control
This parameter Enables/Disables the Tension Torque Bias input function.
This feature is enabled by selecting a Tension Torque Bias input signal source.
Settings:
0 — Disabled
1 — V/I
2 — RR
3 — RX
4 — Panel Keypad
5 — RS485 2-wire
6 — RS485 4-wire
7 — Communication Option Board
8 — RX2 Option (AI1)
154
Direct Access Number — F416
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — No
Minimum — 10
Maximum — 250
Direct Access Number — F420
Parameter Type — Selection List
Factory Default — RX
Changeable During Run — Yes
Direct Access Number — F423
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes