F675
MON2 Terminal Adjustment
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter is used to set the gain of the MON2 output terminal and is used
in conjunction with the settings of parameter F674.
See parameter
F674
for more information on this setting.
FP Terminal Assignment
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter sets the functionality of the FP output terminal to any one of the
user-selectable functions listed in
parameter F669.
As the assigned function changes in magnitude or frequency, the pulse count of
the FP output terminal pulse train changes in direct proportion to changes in the
assigned function.
Note:
The duty cycle of the output pulse train remains at 65 ±5.0 µS.
This parameter is used in conjunction with parameter
Pulse Output Frequency
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter scales the FP output terminal by setting the pulses-per-second
output signal of the FP terminal.
See
F676
for more information on this parameter.
FM Voltage/Current Output Switching
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter is used to select the type of output signal provided at the FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See
F005
for more information on this setting.
Settings:
0 — 0 – 10V
1 — 0 – 20 mA
FM Output Gradient Characteristic
Program ⇒ Terminal ⇒ Analog Output Terminals
This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See
F005
for more information on this setting.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
196
Table 6 on pg. 239
and is enabled at
F669
and F677.
Direct Access Number — F675
Parameter Type — Numerical
Factory Default — 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
Direct Access Number — F676
Parameter Type — Selection List
Factory Default — Output Frequency
Changeable During Run — Yes
Direct Access Number — F677
Parameter Type — Numerical
Factory Default — 3.84
Changeable During Run — Yes
Minimum — 1.00
Maximum — 43.20
Units — Pulses/Second
Direct Access Number — F681
Parameter Type — Selection List
Factory Default — 0–10V
Changeable During Run — No
Direct Access Number — F682
Parameter Type — Selection List
Factory Default — Plus
Changeable During Run — Yes
H9 ASD Installation and Operation Manual
F682