Speed 13 Operation Time; Speed 14 Operation Time; Speed 15 Operation Time - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F552

Speed 13 Operation Time

Program ⇒ Pattern Run ⇒ Operation Time
This parameter sets the run-time for Preset Speed #13.
This time is effective when used with Group Speeds and non-Group Speeds.
If the Auto-Restart function is activated, the search time required for the Auto-
Restart function will be subtracted from the Operation Time setting; resulting
in a shorter run time.

Speed 14 Operation Time

Program ⇒ Pattern Run ⇒ Operation Time
This parameter sets the run-time for Preset Speed #14.
This time is effective when used with Group Speeds and non-Group Speeds.
If the Auto-Restart function is activated, the search time required for the Auto-
Restart function will be subtracted from the Operation Time setting; resulting
in a shorter run time.

Speed 15 Operation Time

Program ⇒ Pattern Run ⇒ Operation Time
This parameter sets the run-time for Preset Speed #15.
This time is effective when used with Group Speeds and non-Group Speeds.
If the Auto-Restart function is activated, the search time required for the Auto-
Restart function will be subtracted from the Operation Time setting; resulting
in a shorter run time.
Preset Speed Operation Mode
Program ⇒ Pattern Run ⇒ Operation Mode
This parameter is used to set the Preset Speed operating mode.
Select Disabled at this parameter to use the speed command only for Preset
Speed operation.
Select Enabled at this parameter to apply the control settings of
the associated Preset Speed while operating in the Preset Speed mode.
Settings:
0 — Disabled (Preset Speed Only)
1 — Enabled (Full Preset Speed Mode)
H9 ASD Installation and Operation Manual
Direct Access Number — F552
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Direct Access Number — F553
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Direct Access Number — F554
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — Yes
Minimum — 0.1
Maximum — 6000.0
Units —
F520
Direct Access Number — F560
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
F561
F575
to
F560
Setting
Setting
Setting
179