F631

ASD Overload

Program ⇒ Protection ⇒ Overload
This parameter is used to protect the ASD from an overcurrent condition. The
standard overload rating of the H9 ASD is 150% operation for 60 seconds.
This setting allows for the overload protection to be switched from the standard
overload detection means (Thermal Detection and Overload) to thermal
detection only.
Settings:
0 — Thermal Detection + Overload
1 — Thermal Detection Only
The Thermal Detection Only selection is used when multiple devices are
installed horizontally as described on
space in between the adjacent devices the ASDs must be derated as described in
Figure 31 on pg.
190.
H9 ASD Installation and Operation Manual
pg.
15. If the installation provides for no
Direct Access Number — F631
Parameter Type — Selection List
Factory Default — Thermal Detection +
Overload
Changeable During Run — No
F631
189