Toshiba H9 Installation And Operation Manual page 257

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

LED
LCD
Display
Display
*OP
Overvoltage
OT
Overtorque
*POFF
Control
Undervoltage
PtSt
Reference Point
UC
Undercurrent
* Reset ignored if active.
H9 ASD Installation and Operation Manual
Description
DC bus voltage exceeds
specifications.
Torque requirement is in excess
of the setting of
F616
or
F617
for a time longer than the setting
of F618.
Undervoltage condition at the 5,
15, or the 24 VDC supply.
Two speed-reference frequency
setpoint values are too close to
each other.
With the Low-current Trip
(F610) parameter enabled, the
output current of the ASD is
below the level defined at
F611
and remains there for a time
longer than the setting of F612.
Possible Causes
• ASD attempting to start into a spinning motor after a
momentary power loss.
• Incoming commercial power is above the specified
range.
• Decel time is too short.
• Voltage spikes at the 3-phase input; install inductive
filter.
• DBR required.
• DBR resistance value is too high.
• DBR function is turned off.
• Overvoltage Stall feature is turned off.
• System is regenerating.
• Load instability.
• Disable the Ridethrough function (F302).
• ASD is not correctly matched to the application.
F616
or
F617
setting is too low.
• Obstructed load.
• Defective Control board.
• Excessive load on power supply.
• Low input voltage.
• Two speed reference frequency setpoints are too close to
each other (increase the difference).
this function sets the low-current trip threshold
249