F303
Retry Selection
Program ⇒ Protection ⇒ Retry/Restart
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic Retry/Restart
function:
Input Phase Loss (Input Phase Failure)
Output Phase Loss (Output Phase Failure)
Output Current Protection Fault
Output Current Detector error
Load side overcurrent at start
Earth Fault (Ground Fault)
Overcurrent During Acceleration
Arm Overcurrent at start-up
DBR Resistor Overcurrent
Low Current
Voltage Drop In Main Circuit
EEPROM Data Fault (EEPROM Fault)
Flash Memory/Gate Array/RAM-ROM Fault
CPU Fault
Emergency Off (EMG)
Communication Error
Option Fault
Sink/Source Setting Error
Overspeed Error
Overtorque
Key Error
External Thermal Error
Externally-controlled Interrupt
See the section titled
System Setup Requirements on pg. 8
on this setting.
H9 ASD Installation and Operation Manual
Direct Access Number — F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
for more information
F303
135