Toshiba H9 Installation And Operation Manual page 111

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F193
V/f Five-Point Setting Voltage 2
Program ⇒ Special ⇒ V/f Five-Point Setting
The V/f Five-Point Setting Voltage 2 establishes the output voltage level that
is to be associated with the frequency setting of
Frequency 2).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.
V/f Five-Point Setting Frequency 3
Program ⇒ Special ⇒ V/f Five-Point Setting
The Custom V/f Five-Point Setting Frequency 3 sets the frequency to be
associated with the voltage setting of parameter
Voltage 3).
See
F190
and
F191
for additional information on this setting.
V/f Five-Point Setting Voltage 3
Program ⇒ Special ⇒ V/f Five-Point Setting
The V/f Five-Point Setting Voltage 3 establishes the output voltage level that
is to be associated with the frequency setting of
Frequency 3).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.
V/f Five-Point Setting Frequency 4
Program ⇒ Special ⇒ V/f Five-Point Setting
The Custom V/f Five-Point Setting Frequency 4 sets the frequency to be
associated with the voltage setting of parameter
Voltage 4).
See
F190
and
F191
for additional information on this setting.
V/f Five-Point Setting Voltage 4
Program ⇒ Special ⇒ V/f Five-Point Setting
The V/f Five-Point Setting Voltage 4 establishes the output voltage level that
is to be associated with the frequency setting of
Frequency 4).
The
F701
parameter setting will determine if the selection for this parameter
appears in the form of a Voltage (V) or as a Percentage (%) of the ASD rating.
The default setting is %.
See
F190
and
F191
for additional information on this setting.
H9 ASD Installation and Operation Manual
F192
(V/f Five-Point Setting
F195
(V/f Five-Point Setting
F194
(V/f Five-Point Setting
F197
(V/f Five-Point Setting
F196
(V/f Five-Point Setting
Direct Access Number — F193
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number — F194
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F195
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
Direct Access Number — F196
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — No
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Direct Access Number — F197
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — V or % (F701)
F197
103

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents