Jog Stop Pattern; Panel Operation Jog Mode - Toshiba H9 Installation And Operation Manual

Toshiba adjustable speed drive installation and operation manual
Hide thumbs Also See for H9:
Table of Contents

Advertisement

F261

Jog Stop Pattern

Program ⇒ Frequency ⇒ Jog Settings
This parameter sets the stopping method used while operating in the Jog mode.
Note:
This parameter setting is used for the Jog operation only. The
Emergency Off stopping method setting of parameter
priority over this setting and changes made here do not affect the
function or setting of parameter F603.
Settings:
0 — Deceleration Stop
1 — Coast Stop
2 — DC Injection Braking Stop

Panel Operation Jog Mode

Program ⇒ Frequency ⇒ Jog Settings
This parameter enables the Jog command to be received from the EOI. When
disabled the Jog command received from the EOI is ignored.
Jog commands may also be received from the Terminal Board. Priority as to
which is allowed to override the other is selected at F106.
The priority selection at
F106
disables the other. The
F106
Settings:
0 — Disabled
1 — Enabled
H9 ASD Installation and Operation Manual
enables the selected source for Jog control and
setting overrides this parameter setting.
Direct Access Number — F261
Parameter Type — Selection List
Factory Default — Deceleration Stop
Changeable During Run — Yes
F603
has
Direct Access Number — F262
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes