FP2 S−LINK Unit
Notes
X (n) 0 to X (n + 7) F indicate input numbers for the FP2.
Y (n) 0 to Y (n + 7) F indicate output numbers for the FP2.
I/O numbers are determined based on the position of the slot
used for installation and the I/O assignments of other units.
With a CPU that has an internal S−LINK, the Channel 1 side is
n = 0 and the Channel 2 side is n = 1.
With S−LINK unit installed in a standard CPU, n = 0.
If both input and output are specified, always specify the I/O
number for the input first.
The I/O setting switch (MODE) settings should not be changed
after the power supply has been turned on. This causes a CPU
error to occur.
The number of input/output points selected for the S−LINK unit
or CPU with S−LINK serves as the number of I/O points for that
unit. When specifying the number of points, be careful of how
I/O numbers have been allotted to other units.
The contents of the settings for No. 9 and No. F are the same
(either one may be selected).
3.2 Specifying the Number of Input/Output Points
I/O Assignments
next page
3 − 5