FP2 S−LINK Unit
Operation
5.4 S−LINK I/O Device Address Recognition
5.4.4

Results and Processing of Address Recognition

If there are no problems
The displayed numeric value matches the actual number of S−LINK I/O devices that are
connected to the S−LINK system. Operation of the FP2 can now be begun.
Explanation
The connection status that is recognized is stored in the EEPROM in the S−LINK unit.
After this, it will not be necessary to press the system SET button when the power supply
is turned on.
Checking for errors in the S−LINK during operation will be carried out based on the
connection status stored in the memory at this time.
If there is a problem
The displayed numeric value does not match the actual number of S−LINK I/O devices
that are connected to the S−LINK system.
Explanation
There is a S−LINK I/O device that has not been correctly recognized.
Turn off the power supply and check carefully for erroneous connections, and to make
sure none of the addresses specified for S−LINK I/O devices have been duplicated.
For information on connections and on specifying addresses, please refer to the
"S−LINK Construction Manual."
After the error is corrected
Carry out the steps described in "5.4.1 Recognizing the Address", once again.