Specifications

2.3
Specifications
2.3
Specifications
Item
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Ambient storage humidity
Breakdown voltage
Insulation resistance
Breakdown vibration
Breakdown shock
Usage environment
Current consumption
Main unit weight
2 − 8
Specifications
FP2 S−LINK unit
0 to 55°C
−20 to 70°C
30 to 85% RH (with no condensation)
30 to 85% RH (with no condensation)
500V AC between S−LINK terminal
block and ground, for 1 minute
1500V AC between S−LINK terminal
block and AC outer terminal, for 1
minute
100MΩ min. between S−LINK termi-
nal block and ground (using 500V DC
mega ohmmeter)
100MΩ min. between S−LINK termi-
nal block and AC outer terminal (us-
ing 500V DC mega ohmmeter)
10 to 55Hz, 1 sweep/minute Multi−amplitude 0.75mm, 10 minutes each in X,
Y, Z directions
2
98m/s
min., 4 times each in X, Y, Z directions
No corrosive gases. No heavy dust.
130mA max.
Approx. 120g
FP2 S−LINK Unit
CPU with S−LINK
500V AC between S−LINK terminal
block and ground, for 1 minute
1500V AC between AC outer terminal
and ground, for 1 minute
500V AC between DC outer terminal
and ground, for 1 minute
1500V AC between S−LINK terminal
block and AC outer terminal, for 1
minute
100MΩ min. between S−LINK termi-
nal block and ground (using 500V DC
mega ohmmeter)
100MΩ min. between AC outer termi-
nal and ground (using 500V DC mega
ohmmeter)
100MΩ min. between S−LINK termi-
nal block and AC outer terminal (us-
ing 500V DC mega ohmmeter)
670mA max.
Approx. 250g