FP2 S−LINK Unit
5.4
S−LINK I/O Device Address Recognition
When an S−LINK unit is being used for the first time, the connection status for the S−LINK
system must be recognized.
Once the connection status has been recognized, it does not have to be done again each
time the system is started up, but the operator must make sure that recognition has been
carried out the first time that the S−LINK unit is used. Following the procedure noted
below, check to make sure that recognition has been carried out.
5.4.1

Recognizing the Address

Set the RUN/CHK. selector switch on the S−LINK unit to the "RUN" position.
If the S−LINK system is being operated for the first time, turn on the power supply and
then press the system SET button.
Explanation
When the system SET button is pressed, the number of connected devices recognized
by S−LINK unit blinks on the address display in hexadecimal (HEX.) number, and then,
a "
" shaped character rotates in the clockwise direction.
If the actual number of connected devices differs from the number displayed above,
since an unrecognized S−LINK I/O device exists, please check for address overlapping,
misconception, etc..
The number of devices is displayed after the power supply is turned on.
15 (hexadecimal) = 21 (decimal) devices
Note
When booster is connected, even if the address of booster is
recognized, it is not included in the number of connected
devices.
5.4 S−LINK I/O Device Address Recognition
Operation
5 − 7