LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
PasswordTime (O)
Params & Display>
Sum/WinterTime (U)
AZL>
Times
Time EU/US (U)
Language (U)
Params & Display>
AZL
DateFormat (U)
Params & Display>
PhysicalUnits (U)
AZL
Params & Display>
Address (U)
AZL>
SendCycleBU (U)
eBUS
Address (U)
Baudrate (U)
Params & Display>
Timeout (U)
AZL>
Modbus
Local / Remote (U)
Remote Mode (U)
SCC Inc.
Default
Range
120min
10-480min
Manual
Automatic
Automatic
S/W time
S/W time US
US
S/W time EU
English
Description
DD.MM.YY
MM-DD-YY
MM-DD-YY
F / psi
F / psi
C / bar
1
30s
10-60s
1
1-247
9600 bit/s
19200 bit/s
19200 bit/s
Parity (U)
no
even
30s
0-7200s
local
remote
Read Only
32-3632 F
W3 (U)
32 F
0-1449 PSI
Sets the length of time before the password times out.
Manual: Daylight savings time disabled.
Automatic: Daylight savings time enabled.
Daylight savings time schedule. US setting starts the first Sunday in April and ends the last
Sunday in October.
See
Selects the language for the AZL display. Options are English, Deutsch, Francais, Espagnol,
Italiano or Portuguese.
Selects the date format. Choices: MM-DD-YY (US) or DD.MM.YY (European).
Either °C / bar or °F / psi can be chosen.
1-8
Sets the LMV5 address for eBUS (job specific).
Sets the cycle time for the LMV5 to send data to the BAS (job specific).
Sets the LMV5 address for Modbus (job specific).
Sets the baud rate of the Modbus port, which is an RJ45 jack located on the underside of the
AZL. Also affects data output. NOTE: To use Modbus, it must be activated at: Operation >
OptgModeSelect .
no
odd
This sets the parity of the Modbus port. Also affects data output.
If no communication occurs for this period, the AZL considers the Modbus to be unavailable.
If the AZL considers the Modbus to be unavailable, then it will make setpoint W1 the current
setpoint. Other Modbus values will remain what they were previously and / or be
overwritten by input through the AZL.
This enables or disables the use of a Modbus conveyed setpoint, setpoint W3.
local
Local - W3 will not be observed.
Remote - if there is no timeout condition and the remote operating mode is automatic, then
setpoint W3 will be observed.
View the Modbus remote mode status: Automatic, Manual, Burner off
W3 is the Modbus conveyed setpoint. Use with operating mode IntLC Bus.
Page 36
HOME
P - LIST
Description
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x