Siemens LMV5 Series Technical Instructions page 275

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
Table of addresses
Function Address Number
Data designation
of words
03/04
0
1
Phase
03/04
1
1
Position of currently active fuel actuator
03/04
2
1
Position of gas actuator
03/04
3
1
Position of oil actuator
03/04
4
1
Position of air actuator
03/04
5
1
Position of auxiliary actuator 1
03/04
6
1
Position of auxiliary actuator 2
03/04
7
1
Position of auxiliary actuator 3
03/04
8
1
Manipulated variable for variable speed drive R
03/04
9
1
Current type of fuel
03/04
10
1
Current output
03/04
11
1
Current setpoint / temperature / pressure
03/04
12
1
Actual value / temperature / pressure
Unit: See address 18 / 19
03/04
13
1
Flame signal
03/04
14
1
Current fuel throughput
03/04
15
1
Current O2 value (LMV52...)
03/04
16
1
Volume unit of gas
03/04
17
1
Volume unit of oil
03/04
18
1
Unit of temperature
03/04
19
1
Unit of pressure
03/04
20
1
Sensor selection
03/04
21, 22
2
Startup counter total
03/04
23, 24
2
Hours run counter
03/04
25
1
Current error: Error code
03/04
26
1
Current error: Diagnostic code
03/04
27
1
Current error: Error class
03/04
28
1
Current error: Error phase
03/04
29
1
Temperature limiter OFF threshold, in
degrees Celsius / Fahrenheit
(in address 129: Temperature limiter
switching differential ON)
03/04
30
1
Supply air temperature, in degrees Celsius /
Fahrenheit (LMV52...)
03/04
31
1
Flue gas temperature, in degrees Celsius /
Fahrenheit (LMV52...)
03/04
32
1
Combustion efficiency (LMV52...)
SCC Inc.
Access
Data
Data type /
format
R
U16
R
S16
Degrees
R
S16
Degrees
R
S16
Degrees
R
S16
Degrees
R
S16
Degrees
R
S16
Degrees
R
S16
Degrees
S16
Percent
R
U16
0= Gas
1= Oil
R
U16
Fire rate
R
U16
Process units
R
U16
Process units
R
U16
Percent
R
U16
0..65534
R
U16
Percent
R
U16
0= m³
1= ft³
R
U16
0= l
1= gal
R
U16
0= °C
1= °F
R
U16
0= bar
1= psi
R
U16
0=Pt100
1=Pt1000
2=Ni1000
3=temp. sensor
4=press. sensor
5=Pt100Pt1000
6=Pt100Ni1000
7=no sensor
R
S32
R
S32
R
U16
R
U16
R
U16
R
U16
R
U16
R
U16
R
U16
R
U16
Percent
Page 5
HOME
Technical Instructions
Document No. LV5-1000
Range
Updating
coding
rate
0...255
Fast
-3... 93°
Fast
-3...93°
Fast
-3...93°
Fast
-3...93°
Fast
-3...93°
Fast
-3...93°
Fast
-3...93°
Fast
0...110 %
Fast
0...1
Fast
0...100 %
Fast
Medium
0...2000 °C
Medium
0...100 bar
0...100 %
Medium
Fast
0...100 %
Fast
0...1
Slow
0...1
Slow
0...1
Slow
0...1
Slow
0...7
Slow
0...999999
Slow
0...999999
Slow
0...0x FF
Fast
0...0x FF
Fast
0...5
Fast
0...255
Fast
0...2000 °C
Slow
32...3632 °F
-100...+923 °C
Slow
-148..+1693 °F
-100...+923 °C
Slow
-148...+1693 °F
0...200 %
Slow
Section 8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1