Siemens LMV5 Series Technical Instructions page 106

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
6)
If parameter OilPumpCoupling is set to Magnetcoupl, the output for the oil pump can be energized in Phase 22 or in Phase 
38, depending upon how parameter IgnOilPumpStart is set.  If parameter OilPumpCoupling is set to DirectCoupl, the output 
will energize with the blower and de‐energize 15 seconds after the blower de‐energizes. 
 
7)
If gas valve proving is performed on startup (immediately after phase 30), the actuators will be in prepurge position.  If gas 
valve  proving  is  performed  on  shutdown  (immediately  after  phase  62),  the  actuators  will  be  in  the  same  position  as  they 
were in phase 62. The actuators will not move during valve proving. 
 
8)
If parameter AirPressureTest is set to activated, the air pressure switch must open after postpurge is complete, causing input 
terminal X3‐02.1 to de‐energize.  The LMV5 will wait about 30 seconds in phase 10 (driving to home position) for the switch 
to open before the LMV5 goes into alarm.  This is done to check for welded contacts in the air pressure switch. If air pressure 
switch alarms are encountered in phase 10, increasing the setpoint of the air pressure switch typically cures this problem. If 
AirPressureTest is set to deactInStby, the air pressure switch is not checked in phase 10 or 12, but the switch must be open 
or the LMV5 will not start when it receives a call for heat. 
 
9)
The  LMV5  can  be  configured  for  different  reactions  to  extraneous  light  (a  flame  signal  when  there  should  not  be  one). 
Depending  on  how  parameters  ReacExtranLight  and  ExtranLightTest  are  configured,  the  LMV5  can  lockout,  block  the 
startup sequence, or ignore it altogether.  The extraneous light test should always be enabled for gas / oil fired boilers.  The 
only time parameter ExtranLightTest should be set to deactivated is for applications such as waste incineration. 
 
10) If direct start is enabled and there is a call for heat after phase 62, the LMV5 will omit phase 78 and will go to phase 79.  In 
phase  79,  the  LMV5  will  check  the  blower  air pressure  switch  with  the  blower  still  running  by  using  a  three‐way  solenoid 
valve (APS checking).   
If the switch checks out, the LMV5 will then proceed directly to phase 24 (driving to prepurge position). 
 
11) Safety Time 1 is defined as the overlap of the ignition spark and pilot valve. Safety Time 2 is defined as the overlap of the 
pilot  valve  and  the  main  fuel  valves.  Interval  1  and  Interval  2  are  stabilization  times  for  the  pilot  and  main  flames, 
respectively. 
 
12) If parameter ContinuousPurge is set to activated, fan output X3‐01.1 will be energized in all phases.  Typically this is used in 
burner applications where return heat may be a problem.   
 
SCC Inc. 
 
 
Page 48 
Technical Instructions 
LV5‐1000 
Section 3 

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents