LEGEND - Password Access: (U)=User, (S)=Service, (O)=OEM, Shaded = Commonly Used, ** = Must Set, X = Has Function, / = Partial Function
Menu Path
Parameter
MinActuatorStep (U)
SW_FilterTmeCon (U)
SetpointW1 (U)
SetpointW2 (U)
Params & Display>
LoadController>
SD_ModOn (U)
ControllerParam
SD_ModOff (U)
SD_Stage1On (U)
SD_Stage1Off (U)
SD_Stage2Off (U)
SCC Inc.
Default
Range
This serves as a deadband on the output of the PID loop to eliminate hunting due to small
load changes. If the PID loop requires a load change less than the setting of this parameter,
1%
0.5-10%
the load will not change. Settings of 5% or above may be counterproductive, not permitting
the boiler to closely match the load which may also cause hunting.
This dampens the pressure or temperature that the LMV5 is reading. Higher values increase
3s
1-10s
the damping and will steady small oscillations in the reading.
W1 is the primary setpoint of the boiler, in units of temperature or pressure depending on
0
Sensor Range
the sensor attached to the LMV5. Setpoint is changed via the AZL52.
Also access at: Operation > BoilerSetpoint .
W2 is a secondary setpoint of the boiler, in units of temperature or pressure depending on
the sensor attached to the LMV5.
0
Sensor Range
Also access at: Operation > BoilerSetpoint .
If the LMV5 is in internal load controller mode 2 (IntLC), the setpoint can be switched to W2
(from W1) by closing a contact between X62.1 and X62.2.
Determines what temp. / press. a modulating burner will cycle on when LMV5 is in any
internal load controller mode. Ignored in external load controller modes.
1%
-50-50%
Can be set at a positive or negative %, either above or below the current setpoint
respectively. Percentage based on current setpoint.
Determines what temp. / press. a modulating burner will cycle off when LMV5 is in any
internal load controller mode. Ignored in external load controller modes.
10%
0-50%
Can be set at a positive or negative %, either above or below the current setpoint
respectively. Percentage based on current setpoint.
Determines what temp. / press. a staged oil burner will engage stage 1.
-2%
-50-50%
Set at a negative %, so that the burner will turn on stage 1 at a set % below the current
setpoint. Percentage based on current setpoint.
Determines what temp. / press. a staged oil burner will disengage stage 1.
10%
0-50%
Set at a positive % so that the burner will turn off stage 1 oil at a set % above the current
setpoint. Percentage based on current setpoint.
Determines what temp. / press. a staged oil burner will disengage stage 2. Set at a positive %
8%
0-50%
so that the boiler will turn off stage 2 oil at a set % above the current setpoint. Percentage
based on current setpoint.
Page 30
HOME
Description
P - LIST
Technical Instructions
LV5-1000
LMV
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
x x x
Section 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents