Siemens LMV5 Series Technical Instructions page 149

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series 
 
 
SensOperPhGas 
Enables two flame detectors to be used on one burner (LMV52 only). 
 
ValveProvingType 
Enables  gas valve proving  on start‐up or shutdown  or both.   This type of  testing 
ensures  that  the  gas  valves  are  closed,  and  that  the  valve  seats  are  in  good 
condition. 
 
StartPointOp 
Can  adjust  which  curve  point  the  LMV5  will  drive  to  after  light  off.    This  setting 
does not affect turndown. 
 
NumFuelActuators  Permits the LMV5 to run dual fuel with a single actuator ‐ two fuel valves on one 
actuator. 
 
ProgramStop 
Stops the LMV5 at a particular phase in the start‐up or shutdown sequence.  This 
is particularly useful when set to Phase 44 for tuning the pilot. 
 
FGR‐Mode 
On  an  LMV52,  this  setting  enables  only  the  Aux  3  actuator  to  be  held  from 
modulating  until  a  certain  temperature  or  time  after  light  off  is  met.    This  is 
usually  used  to  delay  the  use  of  FGR  until  a  certain  time  or  until  a  stack 
temperature is met. 
 
ReleasecontctVSD 
If a VSD is being used, this enables the blower to coast down after post‐purge is 
complete. 
 
O2SensServTim 
This sets a service interval for the O
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
SCC Inc. 
 
 
 sensor. 
2
Page 31 
HOME
Technical Instructions 
Document No. LV5‐1000 
Section 4 