Suggested Ratio Control Curve Commissioning  
 
1. The procedure below assumes the following: 
 
a. Pre‐requisites for Basic LMV51 systems or LMV52 systems (from above) are met. 
b. Procedure for Configuring (Parameterization of) an LMV5 has been done (from above). 
c. This is a first‐time commissioning of the LMV5 and the combustion control curve is blank 
(no points entered). 
d. The burner has been lit off, and is at ignition position. 
e. A calibrated stack gas analyzer is sampling the stack gas and can read %O
f.
The boiler has been warmed up to operating temperature / pressure. 
 
2. If activated, set parameter ProgramStop to deactivated.  This will permit the ratio control curve 
to be commissioned.  The ratio control curve can be found under the menu: 
 
Params & Display > RatioControl > GasSettings > CurveParams 
 
3. Go to Point 1.  Point 1 is automatically set to ignition position values.  When Point 1 is entered, 
the AZL will prompt to "change" or "delete" the point.  "Change" should be selected.  Next, the 
AZL will prompt for "Followed" or "Not followed".  "Followed" should be selected.  All actuators 
and  /  or  VSD  that  have  been  activated  should  show  up  on  this  screen.    If  more  than  one  Aux 
actuator  or  VSD  are  activated,  the  screen  may  need  to  be  scrolled  down  to  show  the  other 
actuators.  If an O
 
NOTE:  Using the "Not followed" option is possible but not recommended for most situations 
since the results of changing the actuator positions in "Not followed" mode cannot be seen 
real time on a combustion analyzer.  When "Followed" is selected, a carat (>) is shown when 
the actuators / VSD are moving to the displayed position.  A colon (:) is shown when the 
indicated positions are reached.  A pound (#) is shown when the Aux 3 FGR actuator is being 
held at position due to a time or temperature‐based FGR hold. 
 
4. If  the  low  fire  point  is  not  known  (maximum  burner  turndown),  adjust  the  Point  1  actuator 
positions  until  maximum  safe  burner  turndown  is  achieved.    Record  the  fuel  flow.    If  the  fuel 
flow is not available, burner head pressure can be used as a last resort. 
 
SCC Inc. 
 sensor is being used and is activated, the O
2
Figure 4‐5:  Point 1 on the Ratio Control Curve 
Page 17 
HOME
 
 
 reading will also be displayed. 
2
 
 
 
Technical Instructions 
Document No. LV5‐1000 
 and ppm CO. 
2
Section 4 