Siemens LMV5 Series Technical Instructions page 247

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diag.
Device
Display
Code
Code
20
21
Internal Fault
61
Basic Unit
22
23
No display of
error (can only be
63
Any #
read out via
eBus)
Any #
01
Internal Fault
LMV5
70
02
Basic Unit
03
04
71
Any #
Manual Lockout Lockout was made manually via contact
Any #
01
Internal Fault
72
02
Basic Unit
03
04
Any #
01
Aux 3
Fault Feedback
80
Actuator
Aux Actuator 3
02
03
Any #
01
Air
Fault Feedback
81
Actuator
Air Actuator
02
03
Any #
01
Gas (Oil)
Fault Feedback
82
Actuator
Gas (Oil) Actuator
02
03
Section 7
Meaning for the LMV5x System
Fault with Base Unit (LMV5)
Fault when calling the "ParAccess()" function
Written EEPROM block unequal RAM block
CRC of page is faulty
Matching fault µC1, µC2 when saving the error page
Unit is error-free
Fault during restoring of lockout information
When reading from EEPROM (initialization)
When test writing in the initialization
No write access to error page in init.
Repetition counter "Internal fault" has elapsed
Plausibility fault in connection with fault entry
Fault in "seterr()"
Fault in "seterr()"
Fault in "error_manager()"
Fault in "storeerr()"
Fault with Connected Actuators
Basic unit has detected wrong state of the auxiliary 3 actuator
CRC error
Key error main loop counter
No feedback for max. number
Basic unit has detected wrong state of the air actuator
CRC error
Key error main loop counter
No feedback for max. number
Basic unit has detected wrong state of the gas actuator
CRC error
Key error main loop counter
No feedback for max. number
Page 39
HOME
Corrective Action
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters form the AZL to the LMV5
4) Replace the LMV5
None
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
This lockout occurs when escape and enter on the AZL
are pressed simultaneously. This lockout also occurs
when the remote reset X4-01.4 is energized when an
alarm condition does not exist.
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
1) This fault occurs when an un-addressed actuator is
connected to the CANBus. Addressing the actuator
should eliminate the fault.
2) Check CANBus cabling. Ensure that all cable shields
(screens) which are located in the cable sheath are
terminated correctly at each actuator, O2 module, and
at the LMV5x...
3) Check each CANBus connector to ensure proper
termination (no conductors exposed on the back of the
plug)
4) If fault occurs sporadically: Reduce electrical noise.
5) If fault occurs constantly: Replace actuator according
to diagnostic code.
SCC Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lmv51.140c1Lmv51.040c1Lmv52.240b1Lmv52.440b1

Table of Contents