Siemens LMV5 Series Technical Instructions page 281

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

LMV Series
Modbus Address / LMV5 Parameter Cross-Reference Guide
Modbus
Description
Address
0
Phase
1
Position of active fuel actuator
2
Position of gas actuator
3
Position of oil actuator
4
Position of air actuator
5
Position of aux 1 actuator
6
Position of aux 2 actuator
7
Position of aux 3 actuator
8
Position of VSD
9
Current fuel
10
Current output
11
Current setpoint
12
Actual value
13
Flame signal
14
Current fuel throughput
15
Current O2 value
16
Gas volume unit
17
Oil volume unit
18
Unit of temperature
19
Unit of pressure
20
Sensor type
21, 22
Startup counter total
23, 24
Hours run total
25
Current error: code
26
Current error: diagnostic
27
Current error: class
28
Current error: phase
29
Temperature limiter off threshold
30
Supply air temperature
31
Flue gas temperature
32
Combustion efficiency
35
Inputs (bits)
37
Outputs (bits)
38
Program stop
39
Load controller operating mode
40
Manual / automatic operation
41
Modbus mode: local / remote
42
Modbus downtime
43
Modbus: operating mode in remote
44
External setpoint W3
45
Predefined output
46
AZL fuel selection
47
Setpoint W1
48
Setpoint W2
49
Weekday
50-52
Date
53-55
Time of day
SCC Inc.
Modbus
LMV5 Parameter
Address
56, 57
58, 59
60, 61
62, 63
64, 65
66, 67
See "Normal
68, 69
Total hours system has been powered
Operation" screen
70, 71
72, 73
74, 75
76, 77
78, 79
80, 81
FlameSig QRI_B
82
Curr Flow Rate
83
Additional sensor: current temperature
Current O2 Value
84-91
PulseValueGas
92
PulseValueOil
93
PhysicalUnits
94-96
PhysicalUnits
97
Sensor Select
98-105
TotalStartCount
106
TotalHours
107
108-110
See "Status/Reset"
111
screen
112
113
TL_ThreshOff
114
SupplyAirTemp
115-122
FlueGasTemp
123
CombEfficiency
124
N/A
125
N/A
126
ProgramStop
127
LC_OptgMode
128
Autom/Manual/Off
129
Local / Remote
130
Measuring range for temperature sensors MeasureRangePtNi
Timeout
131
Remote Mode
132
W3
133
SetLoad
134
CurrentFuel
135
SetpointW1
136
SetpointW2
137
Weekday
400-543
Date
544-711
TimeOfDay
Page 11
HOME
Technical Instructions
Document No. LV5-1000
Description
Hours run on gas
Hours run on oil stage 1
Hours run on oil stage 2
Hours run on oil stage 3
Total hours run (resettable)
Total hours run (not resettable)
Startup counter gas
Startup counter oil
Startup counter total (resettable)
Startup counter total (not resettable)
Total volume of gas
Total volume of oil
Total number of lockouts
AZL5 ASN
AZL5 parameter set code
AZL5 parameter set version
AZL5 identification date
AZL5 identification number
LMV5 ASN
LMV5 parameter set code
LMV5 parameter set version
LMV5 identification date
LMV5 identification number
AZL5 software version
LMV5 software version
Load c ontroller software version
Burner ID
Minimum allowed load on gas
Maximum allowed load on gas
Minimum allowed load on oil
Maximum allowed load on oil
Load limitation end user, modulating
Load limitation end user, multi-stage
Temperature limiter ON differential
Adaption active / inactive
Adaption state
Start adaption
Adaption output
PID proprtional band value
PID integral value
PID derivative value
Lockout history
Fault history
LMV5 Parameter
GasFiring
OilStage1/Mod
OilStage2
OilStage3
TotalHoursReset
TotalHours
SystemOnPower
GasStartCount
OilStartCount
TotalStartCountR
TotalStartCount
Volume Gas
Volume Oil
LockoutCounter
Temp. ColdStart
ASN
ParamSet Code
ParamSet Vers
ProductionDate
SerialNumber
ASN
ParamSet Code
ParamSet Vers
ProductionDate
SerialNumber
SW Version
SW Version
SW Version
BurnerID
MinLoadGas
MaxLoadGas
MinLoadOil
MaxLoadOil
User MaxLoadMod
User MaxLoadStg
TL_SD_On
StartAdaption
StartAdaption
StartAdaption
AdaptionLoad
P-Part
I-Part
D-Part
LockoutHistory
FaultHistory
Section 8