Siemens LMV5 Series Technical Instructions page 252

Linkageless burner management system
Hide thumbs Also See for LMV5 Series:
Table of Contents

Advertisement

Error
Diag.
Device
Display
Code
Code
30
Internal Fault
31
Load Controller
32
Parameter Set
33
damaged
34
35
36
37
38
39
3A
3B
Internal Fault
Load Controller
40
LMV5
Load
A6
Controller
Module
41
42
43
Parameter Set
44
damaged
Parameter
45
Backup Restore
46
4A
Internal Fault
4B
Load Controller
4C
4D
4E
Section 7
Meaning for the LMV5x System
Fault with Base Unit (LMV5) Internal Load Controller
EEPROM does not respond within the expected period of time
Max. number of EEPROM attempts exceeded
Fault during opening of page
Invalid CRC when reading a page
Page cannot be set to FINISH
No access to PID after identification
No access to PID Standard after identification
No reading of EEPROM at identification fault
No EEPROM write access for PID possible
No EEPROM write access for PID Standard possible
No access if reception via COM
Invalid page access
Page too long open
Invalid phase during parameterization of the safety-related
page P_TW
Invalid phase during parameterization of the safety-related
page P_STATUS
Invalid phase during parameterization of the safety-related
page P_SYSTEM
Page has been set to ABORT
Page has been set to RESTO
Page has an invalid status
CAN error
CAN error
CAN error
CAN error
CAN error
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
Reset the unit. Restore parameters from AZL to LMV5 if
necessary.
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Restore
parameters from the AZL to the LMV5
4) If fault occurs continuously, replace LMV5.
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
1) Reset the LMV5
2) If fault occurred after changing a parameter, check
the parameters that were last changed.
3) If fault cannot be rectified by the reset: Download
parameters from the AZL to the LMV5
4) Replace the LMV5
If fault occurs sporadically, reduce electrical noise.
If fault occurs continuously, replace LMV5.
Page 44